![MR ETOS IM Скачать руководство пользователя страница 220](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393220.webp)
7 Operation
Maschinenfabrik Reinhausen GmbH 2019
220
5163667/06 EN
ETOS
®
IM
The data values transmitted over Modbus do not get checked for validity
(valid flag). Therefore, the failure of a sensing elements cannot be detected.
Figure 165: Configuring MR sensor bus
The operation described below is only possible if you access the visualiza-
tion using a computer. You must also have a Parameterizer or Administrator
user role.
Baud rate
You can use this parameter to set the serial interface's baud rate. You can
select the following options:
▪ 9600 baud
▪ 19200 baud
▪ 38400 baud
▪ 57600 baud
▪ 115200 baud
To select the baud rate, proceed as follows:
1. Go to
Settings > Parameters > Sensor bus > Baud rate
.
2. Select baud rate.
3. Press the
Accept
button to save the modified parameter.
Number of databits
You can use this parameter to set the number of databits.
To set the number of databits, proceed as follows:
1. Go to
Settings > Parameters > Sensor bus > Number of databits
.
2. Set number of databits.
3. Press the
Accept
button to save the modified parameter.