7 Operation
Maschinenfabrik Reinhausen GmbH 2019
206
5163667/06 EN
ETOS
®
IM
For the Duval, Rogers, Dörnenburg and IEC 60599 analyses, the values
measured by the sensor have to exceed the following detection limits. If the
measured values are less than the detection limit, the device will use the de-
tection limit value for the calculation.
Gas
Detection limit
H
2
50 ppm
CH
4
10 ppm
C
2
H
2
10 ppm
C
2
H
4
10 ppm
C
2
H
6
10 ppm
Table 58: Detection limits
7.14.2.1 Absolute values
You can display the current absolute measured values of the sensors. Fur-
thermore, a bar chart shows a graphical representation of the measured
value and the set limit values (yellow, red).
Figure 152: Display of absolute values
To display the absolute values, proceed as follows:
► Go to
Information > DGA > Absolute values
.