7 Operation
Maschinenfabrik Reinhausen GmbH 2019
198
5163667/06 EN
ETOS
®
IM
▪ Operating time
▪ Parameter set
– Delay time
– Hysteresis
– Switch-on threshold
Figure 146: Status of cooling stages
To display the status of the cooling stages, proceed as follows:
► Go to
Information > Cooling stages
.
7.13.6 Configuring the frequency-based cooling system control
The optional frequency-based cooling system control function lets you con-
trol the fans in a cooling system using the frequency. The device calculates
the fan speed based on the temperature of the top-oil and the load factor.
The device uses the highest speed derived based on the configured depen-
dencies.
You can set the following parameters for this:
▪ Minimum fan operating time after error: Duration for how long the fans are
to continue running if an error occurs in the cooling system control. The
fans run at full power for this duration.
▪ Minimum fan speed
▪ Maximum fan speed
▪ Upper threshold for top-oil temp.
▪ Lower threshold for top-oil temp.
▪ Upper load factor threshold
▪ Lower load factor threshold