![MR ETOS IM Скачать руководство пользователя страница 196](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393196.webp)
7 Operation
Maschinenfabrik Reinhausen GmbH 2019
196
5163667/06 EN
ETOS
®
IM
7.13.3 Configuring periodic mode
Periodic mode is used to prevent the bearings of the cooling stages from
seizing up as a result of long idle periods. To do this, the cooling stages are
operated for a certain period at regular intervals regardless of the measured
temperature. You can activate/deactivate periodic mode individually for ev-
ery cooling stage (Configuring cooling stages [
The following parameters are available to configure periodic mode:
▪ Activate periodic mode
▪ Switch-on delay: Period after which the cooling stages are to be switched
on for the first time.
▪ Switch-on duration: Period for which the cooling stages are to be switched
on.
▪ Interval: Period after which the cooling stages are to be switched on
again.
Figure 144: General cooling
To configure periodic mode, proceed as follows:
1. Go to
Settings > Parameters > General cooling
.
2. Select the parameter you want.
3. Select the option you want from the list box or enter the desired value.
4. Press the
Accept
button to save the modified parameter.
7.13.4 Configuring alternating mode
If the transformer is equipped with several similar cooling stages, you can
run the stages in alternating mode. In alternating mode, each of the cooling
stages is run in turn to evenly distribute the load of the cooling stages. You
can activate/deactivate alternating mode individually for every cooling stage
(Configuring cooling stages [