7 Operation
Maschinenfabrik Reinhausen GmbH 2019
195
5163667/06 EN
ETOS
®
IM
7.13.2 Configuring load-dependent mode
In load-dependent mode all cooling stages are activated if the load current of
the transformer is greater than the set switching point. You can set the
switching point as a percentage in relation to the transformer rated current.
Once the switch-on delay has elapsed, the cooling stages are activated. To
limit the switch-on current of the cooling stages, they are activated one after
another with a delay time of 60 seconds.
The following parameters are available to configure the load-dependent
mode:
▪ Activate load-dependent mode
▪ Switching point: Switch-on threshold as percentage, in relation to rated
current of transformer.
▪ Switch-on delay: Delay time for switching on the first cooling stage.
▪ Overrun: Period for which the cooling stages remain switched on if the
transformer load current is again less than the set switching point.
Figure 143: General cooling
To configure the load-dependent mode, proceed as follows:
To use this function, you need to activate the corresponding cooling stage
[
1. Go to
Settings > Parameters > General cooling
.
2. Select the parameter you want.
3. Select the option you want from the list box or enter the desired value.
4. Press the
Accept
button to save the modified parameter.