7 Operation
Maschinenfabrik Reinhausen GmbH 2019
160
5163667/06 EN
ETOS
®
IM
Function monitoring
You can use this parameter to activate function monitoring. You can select
the following options:
Setting
Behavior
Off
Function monitoring is deactivated.
Only Auto
Function monitoring is only active in AVR AUTO oper-
ating mode.
Auto and Manual
Function monitoring is active in AVR AUTO and AVR
MANUAL operating mode
Table 50: Activate function monitoring
Hysteresis limit value
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.
Delay time limit value
You can use this parameter to set the delay time in order to delay the issuing
of the event message.
Also refer to
2
7.8.7 Phase symmetry monitoring
If you are measuring the voltage and current with the 3-phase UI 3 measur-
ing module, you can set the maximum permitted differences for voltage and
phase angle between the 3 phases. The difference is determined from the
highest and lowest measured value of the 3 phases.
The following parameters are available for configuring phase difference
monitoring:
▪ ∆U-3ph
▪ ∆U-3ph behavior
▪ ∆U-3ph delay
▪ ∆φ-3ph
▪ ∆φ-3ph behavior
▪ ∆φ-3ph delay