7 Operation
Maschinenfabrik Reinhausen GmbH 2019
158
5163667/06 EN
ETOS
®
IM
Behavior limit value
You can use this parameter to set the behavior of the device when the event
message is issued. You can select the following options:
Setting
Behavior
Off
Tap position monitoring is disabled.
Auto blocking po-
The automatic control does not perform a tap-change operation
in the direction of a higher tap position (p).
You can still perform a tap-change operation in the direction of
a higher tap position (p) in manual mode.
Auto blocking po-
sition-
The automatic control does not perform a tap-change operation
in the direction of a lower tap position (position-).
You can still perform a tap-change operation in the direction of
a lower tap position (position-) in manual mode.
Auto/manual
blocking p
The automatic control does not perform a tap-change operation
in the direction of a higher tap position (p).
You cannot perform a tap-change operation in the direction of a
higher tap position (p) in manual mode.
Auto/manual
blocking position-
The automatic control does not perform a tap-change operation
in the direction of a lower tap position (position-).
You cannot perform a tap-change operation in the direction of a
lower tap position (position-) in manual mode.
Operations counter
The device's operations counter is automatically increased with every tap-
change operation. You can use this parameter to set the number of tap-
change operations, such as for a comparison with the operations counter of
the motor-drive unit.
To set tap position monitoring, proceed as follows:
1. Go to
Settings > Parameters > Tap position monitoring
.
2. Select the parameter you want.
3. Set parameter.
4. Press the
Accept
button to save the modified parameter.
Also refer to
2
Tap position monitoring (optional) [
7.8.6 Bandwidth monitoring
The following limit values are monitored via bandwidth monitoring. The set
bandwidth [
Section 7.3.2, Page 111] is used for this purpose.
▪ Upper bandwidth
▪ Lower bandwidth