11 Technical data
Maschinenfabrik Reinhausen GmbH 2019
64
6107891/02 EN
ECOTAP
®
VPD
®
11 Technical data
11.1 On-load tap-changer type designation
The designation of a particular on-load tap-changer model depends on vari-
ous features, hence ensuring an unmistakable and non-interchangeable on-
load tap-changer designation.
11.1.1 ECOTAP® VPD on-load tap-changer designation
Type designation
ECOTAP® VPD III 100 D – 36 – 09 09 0
ECOTAP® VPD
On-load tap-changer type
III
Number of phases
100
Maximum rated through-current I
rm
[A]
D
Application: Delta
36
Highest voltage for equipment U
m
[kV]
09 09 0
Basic connection
Table 8: Designation of the ECOTAP® VPD® on-load tap-changer
11.1.2 Number of positions and basic connection
The selector must adapt to the number of positions and tapped winding cir-
cuit.
Designation of basic connec-
tion
09 09 0
09
Contact circle pitch of selector
09
Maximum number of operating positions
0
Number of mid-positions
Table 9: Designation of basic connection