6 Mounting
Maschinenfabrik Reinhausen GmbH 2018
36
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Reliable operation of the device in the permitted temperature range requires
that you maintain the following minimum distances to the control cabinet and
to neighboring components:
Minimum distance
To the floor of the control cabinet
88.9 mm (3.5 in)
Corresponds to 2 RU
To the roof of the control cabinet
Between assemblies on the bus bar and assem-
blies on the remote cap rail
Table 8: Minimum distances in the control cabinet
Figure 14: Example depiction of the minimum distances in a control cabinet
For other installation types, contact Maschinenfabrik Reinhausen GmbH.
6.3 Mounting location
In order to ensure safe operation of the device, the device must be mounted
in an enclosure or control cabinet that has the following properties:
▪ Protection against mechanical influences
▪ Assurance of permissible ambient conditions (see Technical data [
tion 12, Page 178] section)
6.4 Mounting the device
You can mount the device in one of the variants described below:
▪ Mounting the device using the cap rail included in delivery
▪ Mounting the device on an alternative cap rail
Observe the following sections when doing so.