12 Technical data
Maschinenfabrik Reinhausen GmbH 2018
178
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
12 Technical data
12.1 Voltage supply
G1 PULS QS3.241
Permissible voltage range
85...276 V AC
88...375 V DC
U
N
: 100...240 V AC
U
N
: 110...300 V DC
Permissible frequency range
50 / 60 Hz
Power consumption
70 W
Table 65: Voltage supply
12.2 Voltage measurement and current measurement
UI 3
Measurement
3 phase
Voltage measurement
U
N
(RMS): 100 V AC
Measuring range (RMS): 19.6...150 V AC
Measuring accuracy (at U
N
, -25...+70 °C): <± 0.3%
Intrinsic consumption: < 1 VA
Measurement category III in accordance with IEC
61010-2-30
Current measurement
I
N
: 0.2 / 1 / 5 A
Measuring range: 0.01...2.1 · I
N
Overload capacity: 12.5 A (continuous), 500 A (for 1 s)
Measuring accuracy (at I
N
, -25...+70 °C): <± 0.5%
Intrinsic consumption: < 1 VA
Phase angle
Measuring accuracy (-25...+70 °C): U
x
/I
x
<± 0.5°; U
x
/U
y
<± 0.3°
Frequency measurement
f
N
: 50 / 60 Hz
Measuring range: 45...65 Hz
Measuring accuracy (-25...+70 °C): <± 0.03%
Table 66: Technical data for the UI 3 assembly