10 Fault elimination
This chapter describes how to rectify simple operating faults.
10.1 General faults
Characteristics/details
Cause
Remedy
No function
▪ Device not starting
No voltage supply
Check the voltage supply
Breaker tripped
Contact Maschinenfabrik Reinhausen GmbH
No function
▪
ERR
LED of CPU I assembly
lights up
Rotary switch of CPU I assembly
moved
Correct position of rotary switch:
▪ 0 position
▪ RUN position
Configuration error
Contact Maschinenfabrik Reinhausen GmbH
Table 63: General faults
10.2 Human-machine interface
Characteristics/details
Cause
Remedy
No display/screen is loaded
Power supply interrupted.
Check the voltage supply.
Error when loading the current
screen in the browser.
Press [F5] key to update the screen.
Fuse faulty.
Contact Maschinenfabrik Reinhausen.
Connection cannot be established
with visualization
Connection cable defective.
Check connection cable.
IP addresses of visualization and
SCADA are in the same subnet.
Check the setting of the IP addresses of the de-
vice and correct where necessary.
PC not in same subnet as visual-
ization.
Check the setting of the IP addresses of the de-
vice and PC and correct where necessary.
Table 64: Human-machine interface
10.3 Other faults
If you cannot resolve a problem, please contact Maschinenfabrik Rein-
hausen. Please have the following data to hand:
▪ Serial number
– Name plate (can be found on CPU assembly)
Please provide answers to the following questions:
▪ Has the software been updated?
▪ Has there previously been a problem with this device?
▪ Have you previously contacted Maschinenfabrik Reinhausen about this is-
sue? If yes, then who was the contact?