7 Operation
Maschinenfabrik Reinhausen GmbH 2021
94
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
6. Press
to leave the parameterization menu.
7.4.17 Display control parameters (F9)
You can use this function to check the set values of the device. Here, the de-
vice successively displays the parameter designation and the set values of
the following parameters and functions:
▪ Parameters P1...P9
▪ Functions F2, F5, F6, F7.1 and F7.2
To check the control parameters, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired function is displayed.
ð
2. Press
to confirm the selection.
ð
The display displays the parameter designation and the set values suc-
cessively at a rate of 1 second.
3. Press
to exit the display.
4. Press
to leave the parameterization menu.
7.4.18 Displaying event memory (E)
The event memory will show you the saved event codes. You can find an
overview of the event codes in the Event messages [
The event memory has 20 memory slots and displays the last 20 entries.
Memory slot 1 is the latest entry, memory slot 20 is the earliest entry. The
device records the number of tap-change operations when an event mes-
sage happens or is reset.
A memory slot entry contains the following information:
▪ Event code
▪ Number of tap-change operations
If an entry only includes the number of tap-change operations and not an
event code, this means that the event code in the previous memory slot was
reset at this number of tap-change operations.
With the exception of event code
E6
, all event codes are reset once the fault
has been eliminated and the next correct tap-change operation has been
completed. Event code
E6
can only be reset by the Maschinenfabrik Rein-
hausen GmbH Technical Service department.