7.4.12 Software update (F4)
You can use this function to perform software updates. Contact Maschinen-
fabrik Reinhausen GmbH if you have any problems when operating the de-
vice.
7.4.13 Invert travel commands (F5)
You can use this parameter to invert the travel commands. You can use this
to adjust the behavior of the device based on how your on-load tap-changer
and motor-drive unit are configured. You can select the following options:
Setting
Meaning
0
Normal configuration:
▪ Lowest voltage (low-voltage side) in operating position 1
▪ Highest voltage (low-voltage side) in operating position n
1
Inverted configuration:
▪ Highest voltage (low-voltage side) in operating position 1
▪ Lowest voltage (low-voltage side) in operating position n
Table 11: Behavior
To set this function, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired function is displayed.
ð
2. Press
to confirm the selection.
3. Press
or
to select the desired option.
4. Press
to confirm the selection.
5. Press
to save the setting.