7 Operation
Maschinenfabrik Reinhausen GmbH 2021
89
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
6. Repeat step 5 until the lowest tap position (Pos. 1) has been reached.
ð
Once the lowest tap position (Pos. 1) has been reached, the display
switches between operations counter, tap position and measured volt-
age.
ð
Manual adjustment is complete.
7.4.9.3 Manual adjustment n+1 (F1.3)
You can use this function to perform a manual adjustment of the on-load tap-
changer starting from the current tap position through to the highest tap posi-
tion (Pos. N). The manual adjustment does not run through the entire regu-
lating range of the on-load tap-changer.
If you perform a manual adjustment with the busbar closed, you must check
that the measured voltage is within the permitted range after the tap change
operations.
To start the manual adjustment n+1 function, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired function is displayed.
ð
2. Press
to confirm the selection.
3. Press
until the desired parameter is displayed.
ð
4. Press
to confirm the selection.
5. Press
to perform one on-load tap-change operation (n+1).
ð
The current measured voltage is displayed.
6. Repeat step 5 until the highest tap position (Pos. N) has been reached.
ð
Once the highest tap position (Pos. N) has been reached, the display
switches between operations counter, tap position and measured volt-
age.
ð
Manual adjustment is complete.
7.4.10 Reading remaining life (F2)
The control unit's integrated energy accumulator is continually monitored.
With the function "Read remaining life", you can request the current status
(as a percentage). If the remaining life is 0%, the function of the energy ac-
cumulator is no longer guaranteed.