7 Operation
Maschinenfabrik Reinhausen GmbH 2021
85
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
4. Press
to confirm the selection.
5. Press
or
to select the desired value.
6. Press
to confirm the selection.
7. Press
to save the setting.
7.4.7 Remote behavior (P9)
You can use this parameter to set the remote behavior of the device in con-
nection with the ECOTAP® VPD® CONTROL PRO control unit. This setting
only has an effect in the EXTERNAL CONTROL operating mode. You can
select the following options:
▪ 0 = local: In the EXTERNAL CONTROL operating mode, automatic volt-
age regulation is performed via the ECOTAP® VPD® CONTROL PRO
control unit. Control commands via SCADA are not possible.
▪ 1 = remote: In the EXTERNAL CONTROL operating mode, you can select
the desired operating mode via SCADA command:
– Automatic voltage regulation via the ECOTAP VPD CONTROL PRO
control unit
– Manual tap-change operations via SCADA commands
To set the remote behavior, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired parameter is displayed.
ð
2. Press
to confirm the selection.
3. Press
or
to select the desired option.
4. Press
to confirm the selection.
5. Press
to save the setting.
7.4.8 Password protection (P10)
The device is equipped with password protection in order to prevent unau-
thorized parameter changes. If you activate the password protection func-
tion, you must first enter the password, before you can display the parame-
terization menu and make settings. If you do not operate the device within 5
minutes, the device is automatically blocked again.