6 Commissioning
Maschinenfabrik Reinhausen GmbH 2021
57
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
6.3.2 Mounting the control unit on an even surface
1. Secure the control unit to the even surface using the fixing brackets pro-
vided for this purpose. Note the dimensional drawing in the appendix.
2. Use one of the lower attachment points to ground the control unit housing.
To do so, crimp a grounding conductor (minimum cross-section 8 mm²)
with a ring-type cable terminal and attach it with washers (contact washer
and safety washer) and M6 bolt.
Figure 36: Mounting the control unit
6.3.3 Connecting control unit at operating site
The following section describes how to make the electrical connection to the
control unit at the operating site.
DANGER
Risk of fatal injury due to electrical voltage!
Danger of death due to electrical voltage when assembling and connecting
the device.
► De-energize the device and system peripherals and lock them to prevent
them from being switched back on.