5 Mounting
Maschinenfabrik Reinhausen GmbH 2021
41
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
5.4.1 Cable recommendation
Please note the following recommendation from Maschinenfabrik Rein-
hausen GmbH when wiring the device:
Cable
Terminal
Cable type
Conductor cross-sec-
tion
Max. length
Power supply and voltage
measurement
X1
Unshielded
1.5 mm² with ferrule
2.5 mm² without ferrule
-
Blocking contact
X3
-
Customer messages
X5
-
RS485; SUB-D
X6
Shielded
0.25 mm²
500 m
Optional control cabinet
grounding
-
Unshielded
≥ 16 mm²
-
Table 7: Recommendation for connection cables
The connection cable between the motor-drive unit and the control unit is
supplied as standard.
DANGER
Danger of explosion!
An impermissibly long connection cable between the motor-drive unit and
control unit can lead to malfunctions of the motor-drive unit and the on-load
tap-changer. This allows the on-load tap-changer to remain in an impermis-
sible operating position. This can lead to an explosion in the transformer.
► Only use the connection cable provided.
► The connection cable may not be altered.
5.4.2 Connecting motor-drive unit and voltage supply
All-pole isolating device
You may connect the control unit only to circuits with an external overcurrent
protection device and an all-pole isolating device, enabling the equipment to
be fully de-energized if required (service, maintenance, etc.).
Suitable equipment includes isolating devices in accordance with
IEC 60947-1 and IEC 60947-3 (e.g. circuit breakers). Observe the properties
of the relevant circuits (voltage, maximum currents) when selecting the cir-
cuit breaker type. In addition, observe the following:
▪ It must be easy for the operator to access the isolating device
▪ The isolating device must be labeled for the device and the circuits to be
isolated
▪ The isolating device may not be a part of the power line
▪ The isolating device may not interrupt the main protective conductor