5 Mounting
Maschinenfabrik Reinhausen GmbH 2021
33
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
5.3 Mounting motor-drive unit
Checking the operating position
The on-load tap-changer has to be in a defined operating position when
mounting the motor-drive unit.
1.
DANGER!
Check the operating position prior to commissioning the
transformer, or ensure that the transformer is de-energized and secured
against reconnection. Failure to do so can lead to death or serious in-
juries.
2. Remove the transport locking plate and store it safely for later use. Do not
leave the sealing module open for long periods in order to prevent soiling
and damage to the mechanics.
Figure 9: Removing the transport locking plate
3. Check the on-load tap-changer operating position. The current operating
position is displayed by the control wheel.
Figure 10: Checking operating position (example illustration)
Содержание ECOTAP VPD 3 30D-24
Страница 131: ......