8. Tighten the screws crosswise with 9 Nm and then crosswise with 16 Nm.
Ensure that the fastenings are not subject to mechanical stress.
Figure 6: Additional seal
5.2 Connecting tap winding and on-load tap-changer take-off
lead
NOTICE
Damage to the on-load tap-changer!
Mounting mistakes will damage the on-load tap-changer and jeopardize
safe operation.
► Connect connecting leads without warping or deforming them and ensure
that no forces are transferred from the connecting leads to the on-load
tap-changer.
► The diagram below shows the areas particularly critical for insulation
spacing. Avoid laying the connection cables in these critical areas.