12 Overview of parameters
Maschinenfabrik Reinhausen GmbH 2021
112
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
12 Overview of parameters
Parameter
Setting range
Factory settings
Current settings
P1: Desired voltage
84…266 V
225 V
P2: Normal regulation
P2.1: Bandwidth B1
0.5…8 %
2 %
P2.2: Delay time T1
5...1800 s
10 s
P3: Fast regulation
P3.1: Bandwidth B2
3%...9%; off
1)
4 %
P3.2: Delay time T2
2 s…(T1 - 1 s / 5 s)
2)
2 s
P4: Voltage blocking
P4.1: Undervoltage blocking
84…266 V
84 V
P4.2: Overvoltage blocking
84…266 V
266 V
P5: Blocking function
0 = inactive
1 = active AUTO/EXTER-
NAL
2 = active MANUAL/
AUTO/EXTERNAL
0
P6: Target position for loss of voltage
P6.1: Set target position
1...9 (17)
1
P6.2 Activate/deactivate function
0 = inactive, 1 = active
0
P7: Number of operating posi-
tions
9 or 17
9
P8: Regulating range
P8.1: Lowest operating position
1…9 (17)
3)
1
P8.2: Highest operating position
1…9 (17)
3)
9
P9: Remote behavior
0 = local, 1 = remote
1
P10: Password protection
P10.1: Set password
0...999
0
P10.2: Activate/deactivate pass-
word protection
0 = inactive, 1 = active
0 = inactive
F1: Automatic/manual adjustment
F1.1: Automatic adjustment
-
-
F1.2: Manual adjustment n-1
-
-
F1.3: Manual adjustment n+1
-
-
F2: Remaining life of the energy
accumulator
-
-
F3: LED function test
-
-
F4: Software update
-
-
F5: Invert travel commands
0 = inactive, 1 = active
0 = inactive