10 Maintenance
Maschinenfabrik Reinhausen GmbH 2021
108
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
4. Press
to leave the parameterization menu.
10.1.6 Checking the temperature blocking
If you operate the on-load tap-changer with alternative insulating fluids, you
must check the function of the temperature blocking [
67]. To do so, proceed as follows:
ü
Check the function of the temperature sensor in accordance with the man-
ufacturer's details.
ü
The
LED is not lit; if this is not the case, resolve the cause of the error.
► Remove the plug at terminal X3 to simulate a blocking signal.
ð
Blocking is active and the LED
is lit.
10.1.7 Oil quality
1. Check the quality of the transformer oil at regular intervals.
2. Determine dielectric strength and water content at an oil temperature of
20°C ± 5°C.
3. The dielectric strength and water content must comply with the limit val-
ues specified in the section "Technical data".
ð
If these limit values are not complied with, change the oil.