MR ComTroll 115C Скачать руководство пользователя страница 10

Page 10 

 

User Manual for ComTroll 115C  

indicators will also respond with information about whether the line voltage (or load current) 

is above or below the set-point used by the indicator for trip and reset of the indicator. 

 

The indicators will respond as follows: 

 

a)

 

If the fault indicator DIP8 is OFF, the indicator cannot be remotely programmed. The 

yellow and green LED (on the indicators) will flash simultaneously. 

 

b)

 

 If the fault indicator DIP8 is ON, the indicator is ready for remote programming. The 

yellow and green LED (on the indicators) will flash alternating. 

 

Point a) and b) will be indicated for 9 seconds. 

 

c)

 

If the line voltage (or load current) is above the threshold for the indicator the green 

LED on the indicator will flash. 

 

d)

 

If the line voltage (or load current) is below the threshold for the indicator the yellow 

LED on the indicator will flash. 

 

Point c) and d) will be indicated for 3 minutes. 

 

 

If the Collector does not get any feedback from one or more of the fault indicators, it will 

close the communication failure relay output to indicate a problem with the communication. 

 

 

2. Communication check and test of relay operation 

 

Press 

RESET REMOTE

 for more than 2seconds but not longer than 4seconds until the Rx/Tx-

LED (yellow LED on the collector) is switched off. 

 

Within maximum 12 seconds, all fault indicators should switch on both the yellow and green 

LED (in the indicator). When the broadcast period is finished (12 seconds) the green LED will 

be switched off.  

The yellow LED in the indicator remains on for period of 10s + address-ID. (e.g in indicator 

with address ‘7’ the yellow LED will be on for 17 seconds). 

After this period the main indication LED (for permanent faults) will flash once and transmit a 

fault message to the collector which will set a pulse on the corresponding relay output. 

 

3. Uploading new settings in the fault indicators (remote programming) 

 

To upload new settings for the fault indicators, SW2 DIP 1 -7 is used. These switches “mirror” 

the setting in the LineTroll 110Eur and LineTroll 110Tur. See tables in section 3.3 for 

programming details. Please note that DIP8 on the fault indicator must be ON to accept 

remote uploading from the collector. 

 

Press 

RESET REMOTE

 for more than 4sec until the Rx/Tx-LED (yellow) and the Running led 

(green) starts flashing on the Collector. 

Содержание ComTroll 115C

Страница 1: ...Page 1 User Manual for ComTroll 115C ComTroll 115C QuickLink Collector User Manual ...

Страница 2: ...th the User Manual for the LineTroll 110Eµr 110Tµr which forms an integral part of an operational QuickLink system Copyright 2011 Nortroll AS All rights reserved All Nortroll products are trademarks or registered trademarks of Nortroll AS Other product names are trademarks or registered trademarks of their respective holders 2011 NORTROLL AS P O Box 133 7601 Levanger Norway www nortroll no ...

Страница 3: ...RESS SETTING 8 Checking the address setting 9 3 FUNCTIONAL DESCRIPTION 9 3 1 LOCAL OPERATION FROM THE COLLECTOR 9 1 STATUS CHECK and RESET OF INDICATION 9 2 Communication check and test of relay operation 10 3 Uploading new settings in the fault indicators remote programming 10 3 2 REMOTE OPERATION FROM SCADA 11 3 3 SETTING UP THE FAULT INDICATORS 11 For LineTroll 110Eur 11 For LineTroll 110Tur 12...

Страница 4: ...e collector Low battery and communication failure alarms This allows connection to any type of RTU with digital inputs for transmitting the fault alarms to a SCADA system 1 2 System configurations A functional system can be set up in different configurations with various numbers of indicators 1 Point to point PtP 2 Point to multipoint PtM with 6 or 9 indicators used in branch points or in poles wi...

Страница 5: ... 1 2 3 4 5 6 7 8 ON RTU 1 2 3 3 2 1 ADDRESS switch 3 ComTroll 115C The rotary switch on the ComTroll 115C called ADDRESS should be set to the number of indicators used in this location in this case 3 The indicators will in PtP mode operate one individual relay output on the ComTroll 115C each The Communication failure Low Battery relay on the ComTroll 115C will be activated if one or more of the t...

Страница 6: ...reen and finally branch 3 must have the last addresses 7 8 9 red See illustration above The indicators on each branch feeder will operate the following relays on the ComTroll 115C Indicator addresses 1 2 and 3 blue feeder operates relay 1 Indicator addresses 4 5 and 6 green feeder operates relay 2 Indicator addresses 7 8 and 9 red feeder operates relay 3 The Communication failure Low Battery relay...

Страница 7: ...s are using the same collector See also section 2 3 about address setting 2 3 Sw2 on ComTroll 115C The DIP switch 2 is only used for setting up parameters in the LineTroll 110Eur Tur See separate section for remote programming of the indicators 2 4 Hardware overview 8 7 10 9 11 4 5 2 3 1 6 1 2 3 4 5 6 7 8 ON Antenna Connector Outputs Inputs Swiches for programming of the fault indicators Address s...

Страница 8: ...l 115C collector unit Active relay outputs will also be reset Reset Collector must take place after changing setting the Address Selector Button is connected in parallel with terminal 4 on the input connector 2 5 Table for address setting ADDRESS Switch on CmT115C Grouping LineTroll 110Eur Tur addresses No of indica tors 1 2 3 4 5 6 7 8 9 0 NOT VALID 1 Point to point mode 1 R1 2 2 R1 R2 3 3 R1 R2 ...

Страница 9: ... information from an indicator which is not connected to the system If the address switch is set to a lower number than the number of indicators connected no alarms will be provided But it will mean that the one or more indicators will not be polled when executing a Test Reset If one or more indicator does not flash after a Test Reset the address switch is most likely set incorrectly 3 Functional ...

Страница 10: ...dicate a problem with the communication 2 Communication check and test of relay operation Press RESET REMOTE for more than 2seconds but not longer than 4seconds until the Rx Tx LED yellow LED on the collector is switched off Within maximum 12 seconds all fault indicators should switch on both the yellow and green LED in the indicator When the broadcast period is finished 12 seconds the green LED w...

Страница 11: ... 3 3 Setting up the fault indicators The user manual for the fault indicator describes in detail the necessary setup of the fault indicator When doing this setting from the ComTroll 115C the meaning of SW2 on the collector will be the same as for the DIP switch on the indicator except for DIP8 This is not used in the ComTroll 115C To set up the indicator parameters set the switches according to th...

Страница 12: ... to indicate permanent or transient faults The setting is done by SW2 DIP8 When the switch is OFF the relay output will be set as soon as the indicator detects a fault regardless whether the fault is transient or permanent The relay will be deactivated 30 seconds after the indicator has detected an energized line If the switch is ON the relay output will be activated only if the indicator defines ...

Страница 13: ...ing the batteries and connect the batteries again Please make sure the red LED on the indicator flash 5 times to confirm a reset 4 2 Antenna The antenna for the ComTroll 115C is provided as three separate items A bracket An Antenna element A coaxial cable Place the male end of the cable through the hole in the end of the bracket and screw the antenna element to the cable Tighten antenna until it i...

Страница 14: ...below NOTE The maximum distance between the antenna position and any of the fault indicators should not exceed 30 meters The communication between the ComTroll 115C and all of the indicators should always be checked after the installation L1 L2 L3 Indicators Cabinet with ComTroll 115C collector Antenna Indicators 7 10m L1 L2 L3 Indicators Cabinet with ComTroll 115C collector Antenna Indicators 5 m...

Страница 15: ... digital inputs are internally connected to the push buttons in the front and provide following functions Time pressed Function 1 0 5sec 2sec Status check of the indicators and resetting of indication 2 2sec 4 sec Test communication and relay operation 3 more than 4 sec Upload new settings in the fault indicators Note Activation of the input is done by shorting the input to GND Supply Voltage 12 2...

Отзывы: