Page 28
Please note:
If configuration settings are changed from the default values for a specific ComTroll 333 RTU
device, the configuration values should only be opened using the
This Device
or
Another
device
option.
If
This Devicetype
is selected, all settings will be set back to the default values specified in the
database.
4. Technical Specifications
Application:
Remote Terminal Unit with GSM communication.
GSM Module:
Wavecom Q64. Quad Band (800/900/1800/1900 MHz)
Inputs:
Open and close status from the end contacts of the switchgear.
6 general optic isolated digital inputs.
4 analog inputs (0-10V or 4-20mA).
Maximum input voltage: 50V dc.
Outputs
Open and close of the switchgear. (Operated remotely or
locally)
6 user specified Normally Open relays.
Maximum switching voltage/current = 200V/1A (AC/DC)
Power supply:
Min:
10Vdc
Max: 15Vdc
Power Consumption: 8mA in idle.
80mA when connected to the GSM Network. This will vary upon
signal strength.
Type test:
EN 1000-4-2,
EN 1000-4-3
ROHS compliant
Mounting:
Snap-on DIN-rail
Temperature range:
-25 to + 70 deg Centigrade operational.
Dimension:
160 x 90 x 80 mm
Weight:
315g