Page 15
Command
Deactivate individual Inputs
Description
Sets configurable 8 character flag in ComTroll 333 RTU.
Each character corresponds with one of the eight digital
inputs:
Char H: Closed
Char G: Open
Char F: Digital input 6
Char E: Digital Input 5
Char D: Digital Input 4
Char C: Digital Input 3
Char B: Digital Input 2
Char A: Digital Input 1
All 8 characters must always be sent.
Char x = 0 --> Input sends alarm upon status change
Char x = 1 --> Input will not send alarms upon status change.
DEFAULT VALUE: 00000000 [HGFEDCBA]
Format
Password 7 HGFEDCBA T
Normal response
3 1 HGFEDCBA 1 T
Error response
3 1 0 0 T
ITU standard
Different network providers uses different ITU standards in the in the interface between the
communication module and the network. ComTroll 333 RTU can be set to use V.32 and
V.110.
Default setting: V.32
Please refer to the local network provider for details.
Command
Select CSD Line Type (ITU standard)
Description
Sets the CSD Line Type used by the communication module
in ComTroll 333 RTU.
X= 0
V.32
X= 1
V.110
Format
Password 9 1 X T
Normal response
3 9 1 X T
Error response
N/A