DCA20SPXU4F • OPERATION MANUAL — REV. #3 (09/18/19) — PAGE 33
Table 10. Inspection/Maintenance
10 Hrs
DAILY
250 Hrs
500 Hrs
or Every
12 Months
3000 Hrs
or Every
36 Months
OTHER
Engine
Check Engine Oil and Coolant Levels
X
Check Fuel Filter/Water Separator Bowl
X
Check Air Cleaner/Element
X
Exhaust System*
5
X
Check for Leaks/Hoses/Clamps*
4
X
Check for Loosening of Parts
X
Change Engine Oil and Oil Filter *
1
X
Clean Unit, Inside and Outside
X
Replace Fuel Filter Elements
X
Check Engine Mounts
X
Service Battery
X
Check Air Intake Hoses
X
Check Fan Belt Condition
X
Check Automatic Belt Tensioner
X
Check Electrical Ground Connection
X
Clean Radiator, Check Cooling System
X
Coolant Solution Analysis, Add SCA's As Required
X
Pressure Test Cooling System
X
Check Engine Speed
X
Test Thermostats
X
Check and Adjust Engine Valve Clearance
X
Test Glow Plugs
X
Flush and Refill Cooling System*
2
2 yrs. or 2000 hrs.
Clean Inside of Fuel Tank
1000 hrs.
Check Crankcase Ventilation Filter
1500 hrs.
Replace Air Cleaner Elements *
3
As Required
Generator
Measure Insulation Resistance Over 3M ohms
X
Check Rotor Rear Support Bearing
X
*
1
During initial operation of a new engine, change oil and filter between a minimum of 100 hrs. and a maximum of 250 hrs. Service interval depends
on type of oil.
*
2
Add “Supplemental Coolant Additives (SCA’S)” to recharge the engine coolant.
*
3
Replace primary air filter element when restriction indicator shows a vacuum of 625 mm (25 in. H
2
0).
*
4
If blowby hose needs to be replaced, ensure that the slope of the blowby hose is at least a 1/2 inch per foot, with no sags or dips that could
collect moisture and/or oil.
*
5
A
ccumulation of carbon (soot, unburned fuel) in the exhaust pipe line and muffler could cause not only system derates but also could lead to fire
incident. To destroy the soot and unburned fuel, run the unit at rated power for some period of time until the exhaust gas become mostly colorless
every 250 hours operation time. The carbon will be easier to be generated when the unit operates at less then 30% of rated power. In this case,
perform the above procedures at shorter interval time.
MAINTENANCE
Содержание WHISPERWATT DCA20SPXU4F
Страница 2: ...PAGE 2 DCA20SPXU4F OPERATION MANUAL REV 3 09 18 19 PROPOSITION 65 WARNING ...
Страница 41: ...DCA20SPXU4F OPERATION MANUAL REV 3 09 18 19 PAGE 41 GENERATOR WIRING DIAGRAM ...
Страница 42: ...PAGE 42 DCA20SPXU4F OPERATION MANUAL REV 3 09 18 19 ENGINE WIRING DIAGRAM ...
Страница 45: ...DCA20SPXU4F OPERATION MANUAL REV 3 09 18 19 PAGE 45 NOTES ...