53
MPSYSTEMS-M-001/06
9.6.1.
Chiller Ambient Temperature Chart
Ambient Temperature Chart
Ambient temperature is not to exceed 95°F or go below 70°F. Loss in in capacity results when ambient
temps are outside the operating range. If set point temperature is greater than 2° below ambient
temperature a loss of capacity is possible.
Pump Model
RF8/VR8
RT/VRT/RF16/VR16
HP PUMP
15264
30528
Circulation Pump
2544
2544
Feed Pump
2544
2544
Total BTU Load
20352
35616
To calculate heat load on machine add total kilowatt or horsepower rating of coolant pumps in machine
tank. 1kW=3412 BTU total kW X 3412 = total BTU's 1HP=2544 BTU total HP X 2544 = total BTU's
If you have any questions, comments, or concerns, please call us at (877) 689-1860 to speak to a Service Technician
MPSYSTEMS-I-001/01 (Ambient Temperature Chart)
100
95
90
85
80
AMBIENT TEMP (F°)
75
70
65
60
20000
15000
10000
5000
0
AMBIENT TEMP NOT TO
EXCEED 95F
40000
35000
AMBIENT TEMP MUST BE ABOVE 70F
30000
25000
Ambient Temp Chiller Capacity
45000
BT
U
/HR
Содержание AK CB20
Страница 15: ...9 MPSYSTEMS M 001 06 4 2 1 Floor Layout R VR SERIES 28 36 15 24 ...
Страница 16: ...10 MPSYSTEMS M 001 06 RF16 RT VR16 VRT SERIES 15 24 38 42 ...
Страница 25: ...19 MPSYSTEMS M 001 06 6 3 3 1 R RA11 Series Control Signal Explanation ...
Страница 26: ...20 MPSYSTEMS M 001 06 6 3 3 1 1 Variable Adaptive Series Control Signal Explanation VR ...
Страница 33: ...27 MPSYSTEMS M 001 06 6 5 3 8JIC to 6JIS Fitting Explanation ...
Страница 72: ...66 MPSYSTEMS M 001 06 10 2 Relief Valve Identifier ...
Страница 76: ...70 MPSYSTEMS M 001 06 JIS JIC Fittings Example 6 3 8 JIS 6 3 8 JIC 8 1 2 JIS 8 1 2 JIC ...
Страница 77: ...71 MPSYSTEMS M 001 06 RF8 Series Flow Diagram ...
Страница 78: ...72 MPSYSTEMS M 001 06 RFC Series Flow Diagram ...
Страница 79: ...73 MPSYSTEMS M 001 06 RA11 Series Flow Diagram ...
Страница 80: ...74 MPSYSTEMS M 001 06 RT Series Flow Diagram ...
Страница 81: ...75 MPSYSTEMS M 001 06 RF16 Series Flow Diagram ...