MGate 5105-MB-EIP
MGate Manager Configuration
3-18
Cyclic: The command is sent cyclically at the interval specified in the “Poll
Interval” parameter.
Data change: The data area is polled for changes at the time interval defined by
Poll Interval. A command is issued when a change in data is detected.
Poll interval
Polling intervals are in milliseconds, since the module sends all requests in
turns, the actual polling interval also depends on the number of requests in the
queue and their parameters. The range is from 500 to 1,200,000 ms.
Endian swap
Data Byte Swapping
None
: Don't need to swap
Byte
: 0x0A, 0x0B, 0x0C, 0x0D becomes 0x0D, 0x0C, 0x0B, 0x0A.
Word
: 0x0A, 0x0B, 0x0C, 0x0D becomes 0x0C, 0x0D, 0x0A, 0x0B.
ByteWord
: 0x0A, 0x0B, 0x0C, 0x0D becomes 0x0D, 0x0C, 0x0B, 0x0A.
There are two phases in changing ByteWord:
1) 0x0A, 0x0B, 0x0C, 0x0D becomes 0x0B, 0x0A, 0x0D, 0x0C
2) 0x0B, 0x0A, 0x0D, 0x0C becomes 0x0D, 0x0C, 0x0B, 0x0A
Read starting address
Station Address. The range is from 0 to 65535
Read quantity
Specifying how many quantities to write.
There are two kinds of quantity units, bit and 16bits, which is associated with
function field. The range is from 1 to 125.
Write starting address Station Address. The range is from 0 to 65535
Write quantity
Specifying how many quantities to write.
There are two kinds of quantity units, bit and 16bits, which is associated with
function field. The range is from 1 to 121.
I/O Data Mapping
To confirm or adjust the internal memory data mapping for both sides, use the web console.