ioLogik E2200 Series
Click&Go
4-18
Host Connection Fail
The
Host Connection Fail
function allows the user to set condition when the connection with the Host
Computer fails. For Example, IF Host Connection Fail, THEN Email to “[email protected]” with message
“Connection with HOST computer have failed! Please react accordingly”.
THEN/ELSE Actions
Under the
THEN
column, you can specify up to 3 actions that will be performed when the
IF
conditions are
satisfied. 3 actions under the
ELSE
column will also be performed when the
IF
is
NOT
satisfied. Possible
actions include changing the status of a DO channel, starting or stopping an Event Counter, or sending a
message by SNMP trap, TCP, UDP, or e-mail.
If Conditions
Result of
AND Logic
Trigger of
Then Actions
Trigger of
ELSE Actions
A1
A2
A3
0
0
0
0
NO
YES
0
0
1
0
NO
YES
0
1
0
0
NO
YES
0
1
1
0
NO
YES
1
0
0
0
NO
YES
1
0
1
0
NO
YES
1
1
0
0
NO
YES
1
1
1
1
YES
NO