Sensor Type
Degree
Count
Ni1000, 0.00618
-60 to 180°C
-600 to 1800
Ni120, 0.00672
-80 to 260°C
-800 to 2600
Channels 6 through 11 are virtual channels. You can click on a virtual channel to configure whether it will return
current averages or deviations for the specified physical channels (RTD-00 through RTD-05).
TC Channels
On the TC Channels page, you can view the status of all TC channels, which includes both physical and virtual
channels. You can click the
Channel Name
to enter settings page on which can set the
Alias Name
.
You can click on each channel to enable or disable it, or to configure the TC input mode. When a channel has
been disabled, the sample rate of the remaining channels will be increased automatically.
The following table is a list of supported sensor types and ranges.
Type
Temperature Range
Count Range
J
0°C
to
750°C
0
to
7,500
K
-200°C
to
1250°C
-2,000
to
12,500
T
-200°C
to
350°C
-2,000
to
3,500
E
-200°C
to
900°C
-2,000
to
9,000
R
-50°C
to
1600°C
-500
to
16,000
S
-50°C
to
1760°C
-500
to
17,600
B
600°C
to
1700°C
6,000
to
17,000
N
-200°C
to
1300°C
-2,000
to
13,000
Voltage: 78.126 mV
- 78.126 mV
to
78.126 mV
-781,260
to
781,260
Voltage: 39.062 mV
- 39.062 mV
to
39.062 mV
-390,620
to
390,620
Voltage: 19.532 mV
- 19.532 mV
to
19.532 mV
-195,320
to
195,320
Содержание ioLogik E2210
Страница 17: ...ioLogik E2200 Series Introduction 1 12 Physical Dimensions Without LCM Unit mm With LCM Unit mm...
Страница 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Страница 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Страница 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Страница 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...