ioLogik E2200 Series
Using the Web Console
5-10
By default, DO and Pulse Output channels are set to “off” when the ioLogik is powered on. You can set a channel
to automatically turn on or begin pulse output when the ioLogik is powered on, by enabling
Power On Setting.
The Interval for
Power On Settings
provides sequential control of the DO outputs while powering up the
ioLogik E2214. The value ranges from 0 to 300 seconds. For example, if all of the DO channels are configured
to be On, and the interval is set to “0” seconds, then all of the DO channels will be switched to On at the same
time. If the DO 0 is set to On and 10 sec, there will be a 10-second delay, and then the DO will be switched to
On as the default status after the ioLogik E2214 system is ready. The Interval with DO default status setting
provides the ability to switch on the DO channels sequentially to avoid the sudden high power burst of the
attached devices and sensors.
You can control how a DO or Pulse Output channel behaves during a network disconnection with the
Safe
Status Setting
and the
Host Connection Watchdog
. With the Watchdog disabled, there is no change to the
channel’s status when there is a network disconnection. With the Watchdog enabled, the
Safe Status Setting
determines whether the channel will turn off, on, or begin pulse output when there is a network disconnection.
The channel will turn on or begin pulse output if
Safe Status Setting
is enabled; the channel will turn off if
Safe Status Setting
is not enabled.
Relay Count Motoring
Two types of relay counts can be recorded in the ioLogik E2214:
Total Counts
and
Current Counts
.
Total
Counts
records how many times a DO (relay) channel has been used. In general, each DO (relay) channel can
be used an average of 100,000 times. Users can monitor these counts to determine when the module should
be replaced, or to switch to a different channel if the total counts approaches the upper limit.
Current Counts
can be reset to zero to record the usage of the external device by monitoring the counts. For example, if D0 0
is connected to an external relay control board, you can monitor the current counts to determine when to
replace the external relay component in advance before it fails.
Last Reset Time
records the time when
Current Counts
was reset. Both
Total Counts
and
Current Counts
will be saved when there is a power failure. The
Last Reset Time
will be saved only when the user manually
presses the
Reset to Zero
button.
Содержание ioLogik E2210
Страница 17: ...ioLogik E2200 Series Introduction 1 12 Physical Dimensions Without LCM Unit mm With LCM Unit mm...
Страница 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Страница 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Страница 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Страница 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...