ioLogik E2200 Series
Using the Web Console
5-9
AO Channels
On the
AO Channels
page, you can configure each AO (analog output) channel by clicking on the channel. The
available options are 0–10 V, and 4–20 mA. You may use the
Power On
field to specify the channel’s initial
value when the ioLogik E2240 is powered on, and the
Safe Status
field to specify the channel’s value when the
ioLogik E2240 enters Safe Status. Note that Safe Status is controlled by the Host Connection Watchdog, which
is disabled by default. If the Host Connection Watchdog is disabled, the ioLogik E2240 will never enter Safe
Status and your Safe Status settings will have no effect.
Relay Output Channel
On the
DO Channels
page, you can view the status of each DO (digital output) channel. Both fixed DO
channels and DIO channels that are acting as DO channels will be displayed.
Click on a channel to see that channel’s configuration options. DO Channels can operate in DO mode or Pulse
Output mode. In DO mode, output is either on or off. In Pulse Output mode, a configurable square wave is
generated.