DR-120 Series 

Hardware Installation Guide 

First Edition, July 2015 

Dimensions 

 

Terminal Pin No. Assignments (TB1) 
PIN No. 

Assignment 

FG 

AC/N (DC+) 

AC/L (DC-) 

 
Terminal Pin No. Assignments (TB2) 
PIN No. 

Assignment 

1, 2 

DC Output V+ 

3, 4 

DC Output V- 

 

 
 

 

 
 

 

 

Mounting Instructions 

Mounting: Mount only as shown in figure, with input terminals 
facing downwards to allow sufficient cooling. 
Admissible DIN rails: TS35/7.5 or TS35/15. 
To attach the DR-120 to the rail: 
1.

 

Rotate the DR-120 backwards, as shown in the figure. 

2.

 

Fit the top of the DR-120 over the top hat rail. 

3.

 

Slide the DR-120 downwards until it hits the stop. 

4.

 

Push the bottom of the DR-120 forward until it snaps into 

place. 

5.

 

Move the DR-120 back and forth to make sure it is locked in 
place. 

 

Installation 

1.

 

To prevent the unit from overheating, always allow sufficient 

clearance around the unit for proper ventilation: 5 mm left and 
right, 40 mm above, and 20 mm below. You should also keep 

a 10 to 15 cm clearance from adjacent devices that act as a 

heat source. 

2.

 

The appropriate mounting orientation is vertical, with input 
terminals on the bottom and output on the top of the DR-120. 

Other mounting orientations, such as upside down, horizontal, 

or table-top, are not allowed. 

 

 
 
 
 
 

 

3.

 

Use copper wire only; the recommended wiring is shown 
below. 
AWG 

18 

16 

14 

12 

10 

Rated Current 

(Amps) 

6-10 

13-16 

16-25 

25-32 

Lead 

cross-section 

(mm

2

0.75  1.00 

1.5 

2.5 

Note:   

When 5 or more wires are connected to the unit, the current 
carried by each wire could be 20% less than the current listed 

above. 
Make sure that all strands of each wire are properly inserted 

into the terminal connection, and that the screw terminals are 

securely fixed to prevent poor contact. If the power supply has 

multiple output terminals, make sure each contact is 
connected to wires to prevent stress on a single contact from 

too much current. 

4.

 

Use wire that can withstand temperatures of at least 80°C, 

such as UL1007. 

5.

 

Suggested fuses and the maximum number of the PSUs that 
can be connected to a circuit breaker at 230 V are shown as 

below: 

Model 

Fuse 

Circuit breakers 
C16 

D16 

DR-120 

F4A/H250W 

6.

 

The recommended wire strapping length is 5 mm (0.197 inch). 

7.

 

Use a slotted type 4 mm screwdriver. 

8.

 

Use the following torque settings for terminals: 
Model 

I/P 

O/P 

DR-120 

10 kgf-cm (9 in-lb) 

10 kgf-cm (9 in-lb) 

 

 

 
 

 

 
 

 

 
 

 

 
 

 

 
 