CONNECTION OF SENSORS TO THE ANALOG NODE
To ensure the operation of the devices connected to the Analog Node and there-
fore a correct detection of the monitoring data, it is essential to follow exactly the
following procedure:
1.
Securely install the Analog Node on the wall, ceiling, floor or pole using screws
and plugs or cable ties.
2.
Open the cover of the Analog Node device. The use of an electric screwdriver
is not recommended.
3.
If necessary, strip the sensor cable by removing the insulating sheath without
damaging the internal wires.
4.
Before proceeding with the connection of a wired sensor, make sure that the
Analog Node is turned off. If necessary, move the “ON / OFF” jumper, positioned
at the top between the two batteries, to the OFF position.
5.
Insert the sensor cable through one of the cable glands located on the under-
side of the Analog Node.
6.
Proceed with the connection of the sensor wires with the corresponding ter-
minals of the Analog Node. The correspondence between the clamp clip and
the sensor wires may vary according to the type of analogue interface of the
sensors to be connected, see the next chapter “Connection to the terminals”:
•
Press and hold the clamp clip with a flat-blade screwdriver.
•
Insert the wire at a 45 ° angle to the clip.
•
Release the clip.
7.
Make sure the correct position of the “Yes / No” jumper located next to each
terminal, see the next chapter “Connection to the terminals”.
8.
It is essential that the correspondence between the sensor and the channel of
the Analog Node (CH.1; CH.2; CH.3; CH.4) is the same previously chosen during
the configuration via the Move Cloud Platform™.
9.
Turn on the Analog Node by moving the “ON / OFF” jumper, located at the top
between the two batteries, to “ON”. If the connection has been made correctly,
the “Power Good” LED on the left side of the card will be on for 2 seconds. If
the “Power Good” LED does not light up, check the charge of the batteries and
their correct installation.
10. Tighten the cable glands making sure not to over-tighten the sensor wires. Fi-
nally close the cover with the appropriate screws making sure that the insula-
ting sheath does not come out of its housing.
“Reset”
botton
Channel clamp
x4
Jumper “Yes/No”
x4
Cable gland
x4
“Power Good”
Led
Lithium batteries
x2
“On/Off”
Jumper
Serigraphs with clamp
positions x4
IMPORTANT
•
Be sure to move the Analog Node off before installing a sensor and
then, if necessary, move the “ON / OFF” Jumper to the OFF position.
•
Be sure to turn on the Analog Node after installation and then move
the “ON / OFF” Jumper to the ON position.
9. Analog Communication Node