ZU25201e_e.doc / Sep-13
Page 13 / 36
5.2.2.
Settings for special applications
Where you find that the standard settings shown before are not suitable for your application,
please go through the following setting options and find out the input levels and characteristics
you need.
DIL1
DIL2
Characteristics of input A
Characteristics of input B
5 6 7
3 4 5 6
x
x
0 0 0 1
TTL level (A)
TTL level (B)
x
x
0 0 1 0
HTL level (A and /A)
HTL level (B and /B)
x
x
0 0 1 1
TTL level (A)
TTL level (B and /B)
x
x
0 1 0 0
TTL level (A and /A)
TTL level (B)
x
x
0 1 0 1
HTL level NPN (A)
HTL level PNP (B)
x
x
0 1 1 0
HTL level NPN (A)
TTL level (B and /B)
x
x
0 1 1 1
HTL level NPN (A)
TTL level (B)
x
x
1 0 0 0
HTL level PNP (A)
TTL level (B and /B)
x
x
1 0 0 1
HTL level PNP (A)
TTL level (B)
x
x
1 0 1 0
HTL level PNP (A)
HTL level NPN (B)
x
x
1 0 1 1
TTL level (A and /A)
HTL level NPN (B)
x
x
1 1 0 0
TTL level (A)
HTL level NPN (B)
x
x
1 1 0 1
TTL level (A and /A)
HTL level PNP (B)
x
x
1 1 1 0
TTL level (A)
HTL level PNP (B)
5.3. Analogue output format
The desired output format of the analogue output can be set by positions 1 and 2 of switch DIL2
DIL2 Output format
1 2
0 0
Voltage 0 … +10 V
With this setting the format depends on the parameter
„Analogue Mode“ which can be set by PC. Since the factory
default setting of parameter “Analogue Mode” is “1”, the
format will be a 0 … +10 V output under default conditions.
0 1
V/- 10 V
1 0
Current 4 – 20 mA
1 1
Current 0 – 20 mA
Содержание ZU 252
Страница 3: ...ZU25201e_e doc Sep 13 Page 3 36...