• Wire size: American Wire Gauge (AWG) 14 to AWG 16
WARNING:
Power source must be disconnected before disconnecting the power connector.
Suitable rated and easily accessible circuit breaker must be incorporated externally to the
equipment when SLX 5000 is connected directly to wiring.
SLX 5000 uses double pole/neutral fusing. Both Line and Neutral have fuses inside.
The onsite source circuit breaker (6 A) must be gang-operated with two poles (single-phase
type).
Procedure:
1
Remove the outer sheath of the cable to no more than 9 mm (0.35 in.).
NOTICE:
Inner insulated wires must not be exposed more than by 13.5 mm (0.53 in.).
a
Strip back approximately 7 mm (0.27 in.) of the inner core insulation.
Figure 39: DC Cable Preparation
7± 2 mm
13.5 mm± 2
9.00 mm± 2
2
Slide up and lift the clamp handle to open the housing lock.
Figure 40: Opening the Housing Lock
3
Separate the housing into its component sections.
Figure 41: Separating the Housing into Sections
4
Insert the gland nut through the other end of the cable.
MN007322A01-B
Chapter 3: SLX 5000 Installation
40