07. TROUBLESHOOTING

INSTRUCTIONS FOR FINAL CONSUMERS

INSTRUCTIONS FOR SPECIALIZED INSTALLERS

Anomaly

Procedure

Behavior

Procedure II

Find source of the problem

• Door/Motor 

doesn't work

• Make sure you have 

a 230V power supply 

connected to the 

control board and if it 

is working properly.

• Still not working

• Consult a qualified

MOTORLINE technician.

1 • Open the control board and check if it has a 230V power supply;

2 • Check the control board input fuses (switch);

3 • If the motor does not work, remove it and send it to the MOTORLINE technical services for diagnosis.

• Door/Motor

doesn’t move

but makes

noise

• Turn off the 230V  

power supply and 

move the door 

manually to check if 

there are mechanical 

problems.

• Found problems?

• Consult an experienced

door expert.

1 • Check all axes and motion systems associated with the door and automatism (shafts, hinges, etc.) to find out what the problem is.

• The door moves 

easily?

• Consult a qualified

MOTORLINE technician.

1 • If the door works, the problem is in the motor. Remove it and send it to the MOTORLINE technical services for diagnosis;

• Door/Motor 

opens but 

doesn't close

•Turn off the 230V  

power supply and 

move the door 

manually to the 

closed position. Turn 

off the building eletric 

board for 5 seconds 

and then turn on.

• The door opened 

but did not closed.

1 • Check if there is any 

obstacle in front of the 

photocells;

2 • Check if any of the door 

control devices (key selector 

and push button) are locked 

and are sending permanent 

signal to the control board;

3 • Consult a qualified

MOTORLINE technician.

A) SAFETY SYSTEMS

(Security systems are opened):

1 • Close with a shunt all control board safety systems (N.C. contacts).

If the automatism starts to work normally, analyze which are the problematic devices.

2 • Remove one shunt at a time to find out which device has the malfunction.

3 • Swap the device with problems for a functional one and ensure that the automatism works correctly with all the other devices. If you find any more 

defective product, follow the same steps until discover all the problems.

• Door/Motor 

doesn’t

make

complete

route

• Turn off the power 

supply and move 

the door manually 

to check if there are 

mechanical problems.

• Found problems?

• Consult an experienced

door expert.

1 • Check all axes and motion systems associated with the door and automatism (shafts, hinges, etc.) to find out what the problem is.

• The door moves 

easily?

• Consult a qualified

MOTORLINE technician.

1 • Make a new programming course in control board attributing the necessary times to open and close with appropriate force.

2 • If that does not work, remove the control board and send it to the MOTORLINE technical services for diagnosis.

NOTE: 

The control board strength must be sufficient to open and close the door without stopping, but a person must be able to stop it with small effort. In 

case of safety systems failure, the door will never cause physical damage to the obstacles (vehicles, people, etc.).

Содержание M1805

Страница 1: ...V4 0 REV 10 2018 M1805 EN USER INSTALLER MANUAL ...

Страница 2: ... SCHEMES TECHNICAL CHARACTERISTICS 03 THE AUTOMATION INSTALLATION MEASURES OPENING DIRECTION 04 PRE INSTALLATION INSTALLATION PROCESS 05 INSTALLATION TECHNICAL CHARACTERISTICS PROGRAMMING 06 THE CONTROL BOARD INSTRUCTIONS FOR FINAL CONSUMERS INSTRUCTIONS FOR SPECIALIZED INSTALLERS 07 TROUBLESHOOTING INDEX RADARS AND PROGRAM SELECTOR CONNECTION 8B 8B 3A 4 6 7 8A 9A 10A 11A 11B 12 12 5 ...

Страница 3: ...pplicable regulations The installer should inform the customer how to handle the product in an emergency and provide him the manual This product is certified in accordance with European Community EC safety standards This product complies with Directive 2011 65 EU of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous substances in electrical...

Страница 4: ...1 Radar CR10MS CR10MS Jumper N C Jumper N O FOTO9S1A Photocells closure 11 12 If you do not use photocells place a shunt between 11 12 inputs FOTO9S1A Photocells open Control board Electric lock magnetic lock 24V continuous power output Battery 24V M1805 Automatism M1601 Radar 12V 12V The electro lock current can not exceed 600mA All connections should be made with the power supply disconnected ...

Страница 5: ... 1 6 7 8 9 10 11 12 13 14 15 2 3 4 K1 K2 5 EN 02 CONNECTION SCHEMES RADARS AND PROGRAM SELECTOR CONNECTION Control board Control board PROGRAM SELECTOR EXTERNAL Radar M1601 INTERNAL Radar M1601 red white purple orange green green white white yellow yellow brown brown green black ...

Страница 6: ... singular doors with interlocking connected to each other you should be aware these connections Only when one of the doors is closed the other can open When using this function if one of the doors is disconnected from the electric current the other will not open Control board of the 1st door 1st door is closed 2nd door started opening Control board of the 2nd door All connections should be made wi...

Страница 7: ...iometer nº4 on the leaf nº2 control board from to create a delay relati ve to the leaf nº1 Operation When using a door with two leaves you should note these connections This function will allow the two sheets work in a coordinated manner All connections must be made with the power supply disconnected In this function if the leaf nº2 encounters an obstacle during closure the micro will give opening...

Страница 8: ...or external opening Ângulo de abertura 0 110 Opening speed 90 2 sec 4 sec Closing speed 90 2 sec 4 sec Pause time in opening 1 sec 20 sec Manual strength 30N Consumption 50W Operating temperature 20 Ϲ 50 Ϲ Door s maximum weight 100kg Accessories output 500mA Eletric lock output 600mA 03 THE AUTOMATION 105mm 75mm 554mm 676mm 516mm 0 20 40 60 80 100 600 700 800 900 1000 1100 1200 Door maximum weight...

Страница 9: ... 112 16 125 106 676 76 100 75 77 X 30 30 MAX 60 516 04 PRE INSTALLATION INSTALLATION MEASURES OPENING DIRECTION 04 PRE INSTALLATION INSTALLATION MEASURES OPENING DIRECTION Opening orientation LEFT Opening direction INSIDE Opening orientation RIGHT Opening direction INSIDE Opening orientation LEFT Opening direction OUTSIDE Opening orientation RIGHT Opening direction OUTSIDE ...

Страница 10: ...fixation plate 08 Slide the automation to the right and se cure it with the 6 screws 02 Remove the 6 screws which hold the au tomation to the wall fixation plate 10 Secure the arm on the automation and set the correct position of the guide to fix it in the door 04 Put the plate against the wall and make the markings pay attention the measures 11 Move the door manually to set the position of the op...

Страница 11: ...necting to the eletric current check if there is some sort of obstacle that hinders the normal operation of the door and if the stopper is well placed 03 Put the K2 and the K1 in the desired position according to the dipper board from the page 11A 04 Turn on the electric current The door will have the following behavior Slowy closes Slowly opens Closes to memorise the position and stays in normal ...

Страница 12: ...s 2 Check if any of the door control devices key selector and push button are locked and are sending permanent signal to the control board 3 Consult a qualified MOTORLINE technician A SAFETY SYSTEMS Security systems are opened 1 Close with a shunt all control board safety systems N C contacts If the automatism starts to work normally analyze which are the problematic devices 2 Remove one shunt at ...

Отзывы: