Manual # 42-02-U001, Rev C1
Place TAPS in Service
When you have completed startup and verification:
• Set the BYPASS/NORMAL switch to the NORMAL position.
• Ensure the AC/TAPS DISCONNECT switch is OFF.
• Install the TAPS cover.
• Turn the AC/TAPS DISCONNECT switch to ON.
Caution
If the BYPASS/NORMAL switch is in the BYPASS position, TAPS will not respond to a
power failure.
Caution
Live voltage in the TAPS unit will now be present on the output wires of the UPS but will be
blocked from the controller by the AC/TAPS DISCONNECT switch through contactor
KM5
.
Danger
Operate the TAPS unit only with the top cover in place to avoid contacting potentially lethal
voltages present on internal components.
Periodic Maintenance
Each TAPS unit should be periodically tested at least every six months.