18
Manual # 42-02-U001, Rev C1
Installing the UPS
Installing the UPS in the base (3kVA) or expansion (6kVA) chassis includes:
• Power and I/O connections
Power and I/O Connections
Figure 10. 3kVA UPS Position on TAPS Baseplate
1. Check that the UPS on/off switch is in the OFF position. NO LEDs on the face of the UPS
should be on.
2. Check that the AC/TAPS DISCONNECT switch is in the OFF position.
3. Remove the stop plate at the front of the chassis (see illustration above).
4. Position the 3kVA UPS on the TAPS baseplate as shown above and defined by rails on
the baseplate. (Physically installing the 6kVA UPS in its separate enclosure is similar.)
Danger
High voltages may be present! Injury or death may result from contacting high
voltages.
Installation and wiring must conform to applicable local and national codes. All work must
be performed by qualified elevator contractors familiar with high voltage and rotating
equipment safety precautions.
When making connections, observe torque ratings specified on the label adjacent to each
terminal. Warranty will be void if connections are not torqued.
High current/high voltage connections must be run in a separate conduit from relay/control
connections.
UPS
Tie-down strap
Stop plate
Содержание TAPS
Страница 6: ...2 Manual 42 02 D001 Rev A 1 September 2003...
Страница 15: ...Installation 9 Manual 42 02 U001 Rev C1 Figure 5 6kVA UPS Enclosure Base Assembly...
Страница 16: ...10 Manual 42 02 U001 Rev C1 Figure 6 6kVA UPS Enclosure Assembly...
Страница 40: ...34 Manual 42 02 U001 Rev C1 6kVA Units The 6kVA unit uses an LCD as well as LEDs...
Страница 42: ...36 Manual 42 02 U001 Rev C1 6 12 12...
Страница 43: ...TAPS Drawings 37 Manual 42 02 U001 Rev C1...
Страница 44: ...38 Manual 42 02 U001 Rev C1...
Страница 45: ...TAPS Drawings 39 Manual 42 02 U001 Rev C1...