Troubleshooting Reference
2-69
element
TM
Series
Fire Recall Main (27)
The car is recalling to the main fire recall floor. At the floor, the car will
behave as configured. Cannot be bypassed.
System Verifies:
- Mode of Operation = Fire Main
Correction:
1. If in error, verify operation of fire/smoke sensors on floors other than
main recall floor.
2. Verify sensors wired according to job prints.
3. Verify System IO > System Inputs, FRM.
Fire Recall: FR1 On (343)
Fire recall initiated by the main fire recall switch (SCE-CPU FR1 ON input
active low). Car recalls to the designated fire floor (usually the lobby).
Correction:
1. Verify System IO > Programmed Inputs > FR1 ON = Off for normal.
Fire Recall: FR1 On2 (344)
A spare input programmed for the FR1 ON2 has been activated.
Correction:
1. Verify spare input programming.
2. Check terminal associated with input.
Fire Recall: FRA (345)
Fire recall initiated by fire sensors in the lobby. SCE-CPU FRA input low.
Car recalls to the alternate fire floor.
Correction:
1. Verify System IO > System Inputs > FRA = On for normal.
Fire Recall: FRS (342)
The dedicated FRS input on the SCE-CPU has been activated.
Correction:
1. Check the main floor fire recall switch.
Fire Recall: FRSA (347)
Fire recall initiated by the fire sensors in the machine room and/or hoist-
way (SCE-CPU FRSA input low). Car recalls to the alternate fire floor.
Correction:
1. Verify System IO > System Inputs > FRSA = On for normal.
Fire Recall: FRSM (346)
Recall initiated by one or more fire sensors at floors other than the ones
at the lobby (SCE-CPU FRS input low). Car recalls to the designated fire
floor (usually the lobby).
Correction:
1. Verify System IO > System Inputs > FRSM = On for normal.
Firmware Update (383)
Controller firmware has been updated.
Flood Operation (30)
Flood operation has been initiated. Cannot be bypassed.
Correction:
1. If in error, verify no programmable Input Pit Flood is configured.
2. Verify System IO > Programmed Inputs > Pit Flood and initiating
device.
Flood Recall (31)
The car is recalling to the designated flood operation recall floor. Cannot
be bypassed.
System Verifies:
- Flood Data = Flood Recall
Correction:
1. If in error, verify no programmable Input Pit Flood is configured.
2. Verify System IO > Programmed Inputs > Pit Flood and initiating
device.
Table 2.15 Touch Screen Event Listings
Event
Description