Part Number: 000016427 Rev 00 08/2020 105
PTCR Operation Check
1. Visually inspect the PTCR. Check for signs of physical damage.
NOTE: The PTCR case temperature may reach 210°F (100°C) while the compressor is
running. This is normal. Do not change a PTCR just because it is hot.
2. Wait at least 10 minutes for the PTCR to cool to room temperature.
3. Remove the PTCR from the ice machine.
4. Measure the resistance of the PTCR as shown. The resistance reading must be
between:
Model
Ohm Value
Amp
PKM0335/PKM0425/PKM0535
10.5 to 19.5
12
Two Terminal PTCR
Fan Cycle Control
Function
Cycles the fan motor on and off to maintain proper operating discharge pressure.
The fan cycle control closes on an increase, and opens on a decrease in discharge pressure.
Specifications
Model
Cut-In
(Close)
Cut-Out
(Open)
PKM0335/PKM0425/PKM0535
335 psig ±5
2310 kPa ±5
275 psig ±5
1896 kPa ±5
Measure Resistance at Ends