8

5.4 Connecting DC Input Power Cables

Before connecting the DC input cable, please make sure that the Inverter “DC SWITCH” in the “OFF” status, otherwise, the high voltage can

bring about life threatening.

Table 5-2 Recommended DC input cable specifications

Conductor cross-section

mm2

Cable diameter range

mm

Range

Recommended Value

2.5

4.0

4.0

4.5

7.8

DC input connector include positive connector and negative connector, as shown in

figure 5-8

.

Figure 5-8 Positive connector and Negative connector

Step 1

Remove cable glands from the positive and negative connectors. Then ,Remove the insulation layer with an appropriate

length from the positive and negative power cables by using a wire stripper as show in

Figure 5-9.

Figure 5-9ConnectingDCinputpowercables(1)

1. Positive power cable

2. Negative power cable

Step 2

Insert the positive and negative power cables into corresponding cable glands.

Step 3

Insert the stripped positive and negative power cables into the positive and negative metal terminals respectively and

crimp them using a clamping tool. Ensure that the cables are crimped until they cannot be pulled out by force less than 400 N,

as shown in

Figure 5-10.

Figure 5-10 Connecting DC input power cables(2)

1. Positive power cable

2. Negative power cable

Step 4

Insert crimped power cables into corresponding housings until you hear a "click" sound. The power cables snap into

place.

Step 5

Reinstall cable glands on positive and negative connectors and rotate them against the insulation covers.

Before performing

step 6

, the

DC

switch is

OFF.

Step 6

Insert the positive and negative connectors into corresponding DC input terminals of the SF series until you hear a "click"

sound, as shown in

Figure 5-11

.

Figure 5-11Connecting DC input power cables(3)

Содержание SF6KTL

Страница 1: ...Solar Inverter SF8KTL...

Страница 2: ......

Страница 3: ...4 2 Pre installation check 4 4 3 Choose an installation location 4 4 4Installing the SF series 4 5 ELECTRICAL CONNECTION 6 5 1 Electrical connection process 6 5 2 Connecting PGND Cables PE 6 5 3 Conn...

Страница 4: ......

Страница 5: ...is manual describes the assembly installation commissioning and maintenance of the following inverters SF6KTL SF7KTL SF8KTL 1 3Target Group This manual is for qualified personnel Qualified personnel h...

Страница 6: ...the SF series inverter before attempting any maintenance or cleaning or working on any circuits connected to the SF series inverter 2 2 Glossary Symbol This section gives a glossary of all the symbol...

Страница 7: ...iew SF8TL series 3 2 Type Label The type labels provide a unique identification of the inverter The type of product Device specific characteristics Certificates and approvals The type labels are on th...

Страница 8: ...15 The connection area must point downwards Do not install horizontally To ensure good heat dissipation and reserve enough space for installing the SF series the SF series is at least 30cm 50 cm 100c...

Страница 9: ...gure 4 5Securinga bracket 1 The hole in the wall 2 Plastic screw socket 3 Tapping screw Step 2Install the SF series 1 Use one hand to hold the handle at the bottom of the SF series and use the other h...

Страница 10: ...the OT terminal and crimp them by using a crimping tool as shown in Figure 5 2 Figure 5 2 Preparing a ground cable Step 2Install the crimped OT terminal flat washer and spring washer on the M6 welded...

Страница 11: ...Connect N to the hole N Connect PE to the hole PE Step 5 Check that all core wires are properly connected Step 6 Secure the adapter to the coupling nut Tighten the adapter to a torque of 1 2 N m Step...

Страница 12: ...r cable 2 Negative power cable Step 2Insert the positive and negative power cables into corresponding cable glands Step 3Insert the stripped positive and negative power cables into the positive and ne...

Страница 13: ...Disconnect the circuit breaker between the inverter and the grid Step 2 Ensure that the DC SWITCH is OFF Step 3 Disconnect the RS485 communication cable Step 4 Disconnect the DC input cable Step 5 Dis...

Страница 14: ...properly connected For details see 5 4 Connecting DC Input Power Cables Step 4Ensure that unused DC input terminals are sealed Step 5Switch on the AC circuit breaker between the SF series and the powe...

Страница 15: ...g Harmonics 3 3 3 A 3 General Data Model SF6KTL SF7TL SF8TL Dimension W H D mm 430 400 160 430 400 160 430 400 160 Weight 16kg 18kg 18kg Cooling Method Natural Cooling Natural Cooling Natural Cooling...

Отзывы: