TOOLS REQUIRED:
www.morningstarcorp.com
GenStar MPPT
4
MOUNTING:
Use mounting template to mark, and drill (3)-1/8 in. screw
hole locations. Drive top screw head to 1/4 in. from flush
with wall. Hang keyhole slot on hanging screw head - see
lower-right illustration. Drive top screw head and (2) lower
screw heads flush with mounting brackets.
3
2
1
WARNING:
Shock Hazard
Verify that the solar, load and battery breakers
and/or disconnects remain open (disconnected)
until after all of the system wiring has been completed.
INSTALLATION SAFETY:
Quick Start Guide
Use following URL to register Morningstar GenStar MPPT:
https://www.morningstarcorp.com/product-registration
AT LEAST
6” (150 mm)
AT LEAST
6” (150 mm)
AT LEAST
3” (75 mm)
AT LEAST
1” (25 mm)
WARM AIR
COOL AIR
GenStar Installation Clearances
[
Choose an indoor mounting location, with no exposure to
sun or water. When mounting, allow for proper air flow, as
seen in upper-right illustration.
SPECIFICATIONS:
GS-MPPT-60
GS-MPPT-80 GS-MPPT-100
Nominal Battery
Voltage
12-24-48V
12-24-48V
12-24-48V
Maximum PV Open-
circuit Voltage
200V
200V
200V
Nominal Maximum
Output Power
800-1600-
3200W
1075-2150-
4300W
1350-2700-
5400W
Maximum
Recommended PV
Input
1
1200-2400-
4800W
1600-3200-
6400W
2000-4000-
8000W
Max. Battery Charging
Current
60A
80A
100A
Rated Load Current
30A
30A
30A
1
150% of
Nominal Maximum Output Power
+
-
12V-24-48V
BATTERY
BATT
(+)
GND
COMMON
NEGATIVES
PV INPUT
PV
(+)
LOAD
(+)
LOAD
(-)
PV
Breaker
Battery
Breaker
Install ferrite core around
PV (+) and (-) wires,
then close and lock core
IMPORTANT: DO NOT CONNECT THE
SOLAR INPUT UNTIL AFTER THE
CONTROLLER HAS BEEN COMMISSIONED
LOAD
(-)
Earth
Ground
Equipment
Grounding
Conductor
Grounding
Electrode
Conductor
+
--
+
+
--
--
--
--
--
--
Install ferrite
core with at
least one
Ethernet wire
loop, then
close and
lock core.
WIRING SCHEMATIC –
see accessory wiring details on p. 5 -
reverse
WIRE SIZE RANGES and TORQUE REQUIREMENTS
Connection Point
Wire Size
Max. Torque
Power Terminals
#8-1/0 AWG
(8.4 - 53.4 mm
2
)
100 in-lb
(11.3 N-m)
Load Terminals
#14-6 AWG
(2.1 - 13.3 mm
2
)
35 in-lb
(4.0 N-m)
Equipment Grounding
Terminal
#14-#2 AWG
(2.1 - 33.6 mm
2
)
50 in-lb
(5.6 N-m)
Battery Voltage Sense
Terminals
#24-16 AWG
(0.2 - 1.3 mm
2
)
5 in-lb (0.56 N-m)
Remote Temperature Sensor
INCLUDED
5 in-lb (0.56 N-m)
Solar Charging System Controller
Contact Information:
www.morningstarcorp.com
Phone: 1-215-321-4457
LEGEND
POSITIVE CONDUCTOR
NEGATIVE
CONDUCTOR
INCLUDES:
Charge controller; Remote
Temperature Sensor (RTS); SD card inside SD card
holder; (1) one-meter MS-CAN Cable; (3) ferrite
cores; mounting template; (4)-#10 mounting screws
IMPORTANT SAFETY INFORMATION:
WARNING:
Shock Hazard
The Morningstar GenStar MPPT must be installed
by a qualified technician in accordance with the electrical
regulations of the installation location.
WARNING:
Shock Hazard
This unit is not provided with a GFDI device. This
charge controller must be used with an external GFDI
device as required by Article 690 of the U.S. National
Electrical Code and depending on the installation location.
CAUTION:
This guide must be used with
the full product manual that includes
important information. Read the GenStar
product manual for all specifications, safety, regulatory and
warranty information, and for all required instructions,
installation procedures, configuration, and operation
details.
OPTIONAL ACCESSORIES:
See product manuals at www.morningstarcorp.com/
support/library/
ReadyRelay (RB-Relay-1)
The ReadyRelay is an expansion block that adds AC or
DC relay dry contact hardware functionality and firmware
control and logic to the Morningstar GenStar MPPT
charge controller.
ReadyShunt (RB-Shunt-1)
The ReadyShunt is an expansion block designed to
display measured branch currents, count Amp-hours for
those branches, and allow net maximum charge current
into a battery, but not exceeding the battery’s maximum
charging rate.
ReadyBMS (RB-BMS-1)
The ReadyBMS provides simple visibility of battery
performance, hands-free settings and optimized battery
control. Through the ReadyBMS, the GenStar MPPT will
report any data variable contained in the battery BMS.
FULL MANUAL INSTRUCTIONS:
Pencil
WARNING:
Equipment Damage or Risk of
Explosion
Never install the GenStar MPPT in an enclosure
with vented/flooded batteries. Battery fumes
are flammable and will corrode and destroy the
GenStar MPPT circuits.
WARNING:
Risk Of Electrical Shock.
NO POWER OR ACCESSORY
TERMINALS ARE ELECTRICALLY ISOLATED
FROM DC INPUT, AND MAY BE ENERGIZED
WITH HAZARDOUS SOLAR VOLTAGE. UNDER
CERTAIN FAULT CONDITIONS, BATTERY COULD
BECOME OVER-CHARGED. TEST BETWEEN
ALL TERMINALS AND GROUND BEFORE
TOUCHING.
CAUTION:
Equipment Damage
Ensure sufficient ventilation - see
clearance illustration on p. 3 - and do not
install in a sealed enclosure. Improper
ventilation will result in over-heating and a
decreased product lifetime.
!
CAUTION: Equipment Damage
Power UP Sequence
- refer to manual’s
LED Indications Section for full details
:
1. Connect Battery/Battery Bank.
2. Connect Solar.
Power DOWN Sequence:
1. Disconnect Solar.
2. Disconnect Battery/Battery Bank.
!
!
Gen
S
tar
MPPT™
NOTE: Actual wire routing and
connection hardware components
may vary.