Moore Industries IPT2 Скачать руководство пользователя страница 7

IPT

  

2

 

The Interface Solution Experts 

7

Figure 2.  Non-Redundant System with Refrigeration Dryer

Cooler

Receiver

5-Micron General
Purpose Filter(s),

One Main or Multiple

on Branch Lines

Refrigeration

Dryer

Extend Branch Line(s) Above Main

Line to Avoid Passing Liquids

0.01-Micron

High Efficiency

Coalescing

Filter(s)

{

Purified Air
For IPT

2

's

Main Line to
Other Branches

Keep Short

Pressure

Regulator

D

Note:  All fi lters should have 
automatic drains and service 
life indicators to show when 
elements need changing.

Calibration

This section provides information necessary to adjust 
and calibrate the IPT

2

.  Each unit is calibrated and 

checked at the factory prior to shipment.  Before 
installation, every IPT

2

 should be checked by the user 

for proper operation.  Generally, these checks, which 
are specifi ed under Calibration Procedures, require 
little or no adjustment.

Adjustments

The IPT

2

 has Zero and Span adjustments located 

on its front panel.  The type of potentiometer used 
with these adjustments usually require 15 turns of 
the shaft to move the wiper from one end of its range 
to the other.  It is equipped with a slip clutch at each 
end to prevent damage if the adjustment is turned 
beyond the wiper stop.  Usually a slight change can 
be felt when the clutch is at the end of a range (i.e., it 
is slipping).  However, if this change is not felt, either 

end can be reached by turning the shaft 15 turns in 
the desired direction.  

Turning these potentiometers clockwise causes the 
related output to increase in quantity or become more 
positive; while turning them counterclockwise causes 
the related output to decrease in quantity or become 
more negative.  

The Zero and Span potentiometers provide an 
adjustment range of ±10% of full scale.

Calibration Equipment

 

Table 2 lists the equipment required to calibrate the 
IPT

2

.  This equipment is not supplied with the unit and 

must be provided by the user.

Table 2.  

Calibration Equipment

Equipment

Adjustable current source

DC milliammeter

Instrument air supply

Air pressure gauge

Air pressure gauge

Phone tip probes (2)

Pneumatic test coupler 
MII P/N 163-202-00

Pneumatic load

Characteristics

0-50mA output

Accurate to ±0.05%

Filtered

Accurate to ±2%

Accurate to ±0.1%

Must have 2mm (0.8 in) diameter tips, .5 inch long

For IPT

2

s with optional test jacks

Volume of 7.5 cubic inches (approx. 120 milliliters)

Purposes

Simulate input signal

Measure input signal

Air supply

Measure air supply pressure

Measure output pressure

Easy access to input signal (optional)

Easy monitoring of output pressure (optional)

Provide standard load for testing (per IEC spec. #770)

Содержание IPT2

Страница 1: ...IPT2 IPT 2 July 2016 170 730 00G Current to Pressure I P Transmitter All product names are registered trademarks of their respective companies Current to Pressure I P Transmitter...

Страница 2: ...Information 5 Application Information 6 Calibration 7 Adjustments 7 Calibration Equipment 7 Test Jacks 8 Calibration Setup 8 Calibration Procedure 8 Installation 9 Mounting 9 Installation in Hazardou...

Страница 3: ...r documentation is missing this number is used to identify equipment characteristics The model number for the IPT2 is located on a label on the side of the unit Serial Number Moore Industries maintain...

Страница 4: ...FA11 FA12 See Table 1 for more information Housing DIN Aluminum DIN style housing assembly WTI Rain proof as de ned by NEMA 3R FA7 or FA8 required WTIP Rain proof as de ned by NEMA 3R with plate and...

Страница 5: ...on temperature pressure and the relative humidity of the air Su cient water must be removed to lower the dew point of the air to a temperature below ambient The dew point at line pressure is expressed...

Страница 6: ...on to prevent oil contamination of the desiccant as well as downstream ltration to prevent desiccant nes from introducing new contamination The service life of an IPT2 is directly proportional to the...

Страница 7: ...he wiper stop Usually a slight change can be felt when the clutch is at the end of a range i e it is slipping However if this change is not felt either end can be reached by turning the shaft 15 turns...

Страница 8: ...illustration of a typical calibration setup including optional equipment To check or calibrate the IPT2 connect the unit as shown in this illustration Calibration Procedure There are two options show...

Страница 9: ...the unit into place until the retaining lever snaps up ush be neath the handle To remove an IPT2 press down on the retaining lever and lift the unit out by the handle Note Check valves in the headers...

Страница 10: ...be used when the IPT2 is installed in a Class I Division 2 location Australia New Zealand ANZEx Installations Certi cate No ANZEx 09 3000X Nonincendive Type n application Ex n Marking Code Ex n IIC T6...

Страница 11: ...D for 2mm 0 8 in Dia Phone Tip Plug Used in FA3 FA4 FA8 FA10 FA11 and FA12 IPT CURRENT PRESSURE TRANSMITTER IN IN SPAN ZERO 39mm 1 54 in 2 Zero Adj Span Adj T T Pneumatic Test Jack Used in options FA3...

Страница 12: ...ibed in the Maintenance section Operation Reverse output operation Once adjusted and installed the IPT2 operates unattended except for occasional cleaning of the air supply lters If a malfunction is i...

Страница 13: ...ly and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall no...

Отзывы: