December 2016  

170-775-00

G

Current-to-Pressure

 

(I/P)

 T

ransmitters

Current-to-Pressure  

(I/P) Transmitters

Содержание IPH2

Страница 1: ...IPH2 IPX2 IPH 2 IPX 2 December 2016 170 775 00G Current to Pressure I P Transmitters Current to Pressure I P Transmitters...

Страница 2: ...Calibration 7 Necessary Equipment and Calibration Preparation 7 Calibration Process 7 9 Installation 10 Phase One Mounting 10 Phase Two Electrical Connections 10 Phase Three Pneumatic Connections 11 H...

Страница 3: ...c signal so that an electronic based system such as a DCS PLC or PC can control a pneumatic actuator valve or damper drive Available models accept a wide range of current inputs 4 20mA 4 12mA and 12 2...

Страница 4: ...g of 15psig Voltage Drop 5V maximum Air Consumption Dead ended At 3 15psig output 20psig supply average steady state consumption of 4 7SCFH min 4 2SCFH 3psig max 5 2SCFH 15psig 40psig supply max 9SCFH...

Страница 5: ...ly attached Do not attempt to remove They may be installed on either side of the unit by the factory Natural gas vent NG option See Pneumatic Connections section 166 6 5 117 4 6 154 6 1 Manual overrid...

Страница 6: ...m 2 7 in 16mm 0 65 in 51mm 2 0 in 83mm 3 3 in 1 4 NPT FEMALE PNEUMATIC INPUT PORT 163mm 6 4 in 135mm 5 3 in WITH FR1 OPTION 1 4 NPT FEMALE PNEUMATIC INPUT PORT UNUSED PORT IS PLUGGED CONDUIT WIRE ENTR...

Страница 7: ...e for minimum values Each is equipped with a slip clutch to prevent damage if the adjustment is turned beyond the wiper stop Note Always use clean dry instrument air when calibrating or operating the...

Страница 8: ...e 4 IPX2 Calibration Setup IPX 2 SELECTABLE OUTPUT ZERO SPAN ZERO SPAN PS PS PNEUMATIC TEST LOAD REGULATED INSTRUMENT AIR SUPPLY PRESSURE GAUGE 1 ACCURACY 2 PRESSURE GAUGE 2 ACCURACY 0 1 _ ADJUSTABLE...

Страница 9: ...itoring the output To calibrate a reverse output unit perform the following 7 For IPX2 new versions introduced in 2013 only check switch is set to Reverse see Figure 5 8 Check unit zero setting Monito...

Страница 10: ...essary for IPX2 NG1 or NG2 installation For all units except the IPX2 NG1 or NG2 connect positive lead to the PS terminal and negative lead to the PS terminal Tighten the terminal screws until snug Ca...

Страница 11: ...rest as dictated by local environmental and safety regulations Indoor natural gas operations are typically monitored to maintain safety conformance outside the lower and upper explosion limits LEL and...

Страница 12: ...cellement doit tre install moins de 457mm du bo tier En Classe 1 Division 2 ce produit doit tre install conform ment 170 775 00 Special Conditions of Use The following instructions must be adhered to...

Страница 13: ...tus shall be protected from impact Intrinsically Safe Applications Certificate No ANZEx 09 3000X Standards AS NZS 60079 0 2005 Explosive atmospheres Equipment General requirements AS NZS 60079 11 2006...

Страница 14: ...period limits 2 If a change in the relationship between the input and output is detected attempt a re calibration of the unit 3 If the response time lengthens or if the span drops check the system for...

Страница 15: ...stries is recognized as the industry leader in delivering top quality to its customers in products and services We perform a battery of stringent quality assurance checks on every unit we ship If any...

Страница 16: ...16 Demand Moore Reliability IPH2 IPX2 Current to Pressure I P Transmitters...

Страница 17: ...Demand Moore Reliability 17 IPH2 IPX2 Current to Pressure I P Transmitters...

Страница 18: ...18 Demand Moore Reliability IPH2 IPX2 Current to Pressure I P Transmitters...

Страница 19: ...y and not to Buyer s customers or the users of Buyer s products unless Buyer is an engineering contractor in which case the policy shall extend to Buyer s immediate customer only This policy shall not...