Programmable Multi-Axis Servo Drive Power Supply Unit Operation Manual
ID no.: CA97556-001 Date: 03/2015
moog
54
Commissioning
y
Set the mains frequency
P-0452
.
Figure 4.2 Parameter editor - parameter
P-0452
NOTE:
For the parameters to take effect even after a restart, the changed settings
must be permanently saved to the device and a 24 V reset performed.
Save setting
1.
To save the parameter setting on the device click the "Save setting permanently
to device" button.
2.
It is also possible to save the parameter data set to the connected PC as a
file. To do so, click the "Save current device setting to file" button, select the
desired directory and click "Save" to confirm.
Figure 4.3 Save setting
1
2
4.2.5
Setting the mains voltage and frequency of the supply
system
4.
The Power Supply Unit is factory-configured to a 3 x 400 V AC (50 Hz) system. If the Power
Supply Unit is to be operated on such a system, continue with step 5. If the Power Supply Unit
is to be operated on a different system, parameters
P-0307
Mains voltage and
P-0452
Mains
frequency must be set to the corresponding values.
NOTE:
Only the fixed mains voltages 400 V, 460 V and 480 V and the mains
frequencies 50 Hz and 60 Hz can be set.
The Power Supply Unit regulates the DC link voltage to an internally preset fixed value.
At an input voltage of 400 V
AC
the DC link voltages 650 and 770 V
DC
are possible. At an
input voltage of 460 and 480 V
AC
the DC link voltage 770 V
DC
is possible.
y
Set the mains voltage
P-0307
.
Figure 4.1 Parameter editor - parameter
P-0307