Moog ACV with CANopen bus interface
7 Servo valve functions
Flow control
B99224-DV018-D-211, Rev. A, October 2018
224
7.12.9.2 Object 0x5220: Actual value high pass filter frequency
This parameter holds the cut off frequency in Hertz of the high pass filter.
7.12.9.3 Object 0x5221: Actual value proportional gain
This parameter holds the proportional gain for the flow actual value.
7.12.9.4 Object 0x5222: Actual value parameter
By default this parameter is pointing to <FlwActualValue> (0x5223) as feedback input for the axis velocity
controller. But also each other signal can be mapped to the feedback input.
Value description
This pointer contains a combination of index, sub-index and length of the parameter to be used. It may only
refer to parameters with a bit length of 0x10.
The default value is 0x52230110, which refers to the <FlwActualValue> (0x5223), sub-index 0x01 with a
length of 16 bit (16 = 0x10).
ValveFlowControl
Index
Sub-index
Parameter name
Data type
Access
Per-
sis-
tence
Value range
Default
0x5220
0
FlwActualValueFilterFrequence
FLOAT32
rw
Y
FLOAT32
20.0
ValveFlowControl
Index
Sub-index
Parameter name
Data type
Access
Per-
sis-
tence
Value range
Default
0x5221
0
FlwActualValueGain
FLOAT32
rw
Y
FLOAT32
1.0
ValveFlowControl
Index
Sub-index
Parameter name
Data type
Access
Per-
sis-
tence
Value range
Default
0x5222
0
FlwActualValueParameter
UINT32
rw
Y
UINT32
0x52230010
<FlwActualValueParameter>
Byte
3
2
1
0
Description
Index MSB
Index LSB
Sub-Index
Parameter bit length:0x10
Default
0x52
0x23
0x01
0x10
Table 88: Possible values of parameter <FlwActualValueParameter> (0x5222)