Page 36
PL52DF* Indoor Gas Fireplace
XG0218 - 160215
Maintenance
SIT Proflame 2:
The following is a troubleshooting chart of possible problems:
If your fireplace still does not operate correctly, consult your local Montigo dealer.
All service and repairs should be performed by a qualified Technician.
All spare parts, optional fans, and optional trim finishes are available from your local Montigo dealer.
PROBLEM
SOLUTION
Pilot Igniter won't spark
1. Check the MAIN ON-OFF switch (typically located
below the valve cover) and turn ON
2. Ensure main power is ON or new batteries are installed
in the remote control and backup battery pack (if available).
3. Check the 3.15A fuse in the control box and replace
if necessary
Pilot Igniter sparking, but Pilot
burner will not light
1. Verify the Inlet and Manifold Gas Pressure are within
acceptable limits
2. Check all connections to gas valve
3. Check connection to stepper motor (if available)
Pilot lights , but Main burner will
not Light
1. Check and verify all wiring connections as per the
wiring diagram.
2 . Verify the inlet and Manifold Pressure are within
acceptable limits
Pilot lights , but Main burner will
not Light and igniter continues
to spark
1. Check the Pilot Flame Sensor Rod and clean with
steel wool or similar.
2 . Check the Pilot hood and clean with steel wool if dirty.
3. Adjust pilot flame using the pilot adjustment screw if
the pilot flame is too long or too short (Flame should fully
engulf the sensor rod and must be stable).
4. Check and make sure the ground wire from the pilot
is connected to the fireplace body.
Troubleshooting: