39
Appendix
xg0227 - 112718
Units with tempered glass doors are vulnerable to rapid and/or extreme
changes in temperature (thermal shock). take care to prevent water
from contacting the fireplace, especially if it is hot.
Notice
This fireplace may be installed into outdoor locations provided they are suitably protected from direct water impingement. However, all installation
clearances in the appliance manual must be observed. Framing, clearances to combustibles, Mantel heights, Facing Requirements, Venting
Installation, etc. use supplied safety screen.
Indoor fireplace in protected outdoor applications
Notes
•
overhang requirements must be applied to both the front and sides of the
fireplace
• Indoor see-through models cannot be installed as indoor/outdoor
fireplaces, as air flows through both sides of the fireplace.
• If the fireplace will be in contact with salt water, then an outdoor fireplace is
recommended
• Follow all building codes, including those addressing fireplace penetration
of an exterior building envelope
Dimension "A"
X .75
= min. overhang depth
The overhang must extend at least 75% of the roof line height (A)
Height is measured from bottom of fireplace opening to the ceiling
•
Follow all product installation instructions; including framing, clearances to
combustibles, mantel heights, Facing Requirements, venting installation,
etc. use supplied safety screen.
•
All wiring connections to line power shall be in accordance with outdoor
requirements of; NECA NFPA 70 in the USA Canadian Electrical Code, CSA
c22.1 for canada.
• The Fireplace is not to be operated in temperatures below freezing (0°C I
32°F)
Example formula
Min. overhang =
A x 0.75
For example: if
distance A is 84", the
overhang must extend
at least 63"
See through fireplace
Single sided fireplace
See table for
min. overhang
depth
See table for
min. overhang
depth
Bottom edge of
fireplace opening
Outdoor area
Outdoor area
Outdoor area
Outside wall
Outside wall
A
A
"A" dimension is
from bottom of
fireplace opening
to bottom edge of
overhang
"A" dimension is
from bottom of
fireplace opening
to bottom edge of
overhang
Fireplace cannot
penetrate building
envelope