NICE5000 User Manual 7 Description of Function Codes
- 171 -
In normal running state, if the continuous motor running time in the same direction between
two adjacent floors exceeds the setting of this parameter but no leveling signal is received,
the system will perform protection.
This parameter is mainly used for over-time protection in the case of steel rope slipping on
the traction sheave.
If this parameter is set to a value smaller than 3s, it becomes invalid.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F9-03
Accumulative working hours
0–65535
0
h
●
F9-04
Accumulative running hours
0–65535
0
h
●
F9-05
Accumulative working days
0–65535
0
day
●
These parameters record the accumulative running and working time.
The working time counts the time since use, regardless of running or stop.
The running time counts only the elevator running time.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F9-06
High byte of running times
0–9999
0
-
●
F9-07
Low byte or running times
0–9999
0
-
●
Running times of the elevator = F9-06 x 10000 + F9-07.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
F9-12
Clock: year
2000–2100
2010
YYYY
☆
F9-13
Clock: month and day
1.01–12.31
301
MM.DD
☆
F9-14
Clock: hour and minute
0–23.59
0
HH.MM
☆
These parameters are used to set the current date and time of the system.
Group FA: Auxiliary Parameters
Function Code
Parameter Name
Setting Range
Default
Unit
Property
FA-00
Group FA security password 0–65535
01000
-
●
You are allowed to view and modify group FA parameters only after entering the security
password.
Function Code
Parameter Name
Setting Range
Default
Unit
Property
FA-01
Display in running state
1–65535
65535
-
☆
It is used to set the running parameters displayed on the operation panel when the elevator
is in the running state.
FA-01 includes 16 binary bits, each defining a parameter. A total of 16 parameters can be
can be displayed during running.
Содержание NICE 5000
Страница 1: ...5000 5000 User Manual 5000 Integrated Elevator Controller Data code 19010314...
Страница 15: ......
Страница 16: ...1 Safety Information and Precautions...
Страница 23: ...1 Safety Information and Precautions NICE5000 User Manual 22...
Страница 24: ...2 Product Information...
Страница 34: ...3 Mechanical and Electrical Installation...
Страница 71: ...4 Use of the Commissioning Tools...
Страница 79: ...5 System Commissioning and Functions...
Страница 99: ...6 Function Code Table...
Страница 130: ...6 Function Code Table NICE5000 User Manual 128...
Страница 131: ...7 Description of Function Codes...
Страница 201: ...8 Troubleshooting...
Страница 220: ...8 Troubleshooting NICE5000 User Manual 218...
Страница 221: ...9 EMC...
Страница 230: ...9 EMC NICE5000 User Manual 228...
Страница 233: ...5000 5000 User Manual 5000 Integrated Elevator Controller Data code 19010314...