background image

Room thermostats

Functions

Features

Technical Information

Alpha-Thermostat

Alpha-Thermostat Standard

AR 20.. S2 (230 V) | AR 40.. S2 (24 V)

Application

General information

The Alpha-Thermostat 20../40.. S2 is a PI thermostat for the control

of thermoelectric actuators (e. g. OEM actuator). The output voltage

is switched on or off depending on the difference between the room

temperature measured by the thermostat (actual value) and the

desired temperature (set value). The bigger the difference is between

set value and actual value, the longer are the switching cycles. When

the room temperature approaches the set temperature, the switching

cycles of the output voltage are reduced and find their balance at

an almost constant value corresponding to the heating power for

this room.

Valve protection function (only NC)

If an actuator is not triggered during more than 24 hours of normal

operation, the electronic system switches the actuator for 6 minutes

once every 24 hours. This prevents the thermostat valves from clogging

outside the heating season.

Antifreeze protection

If the set value element of the Alpha-Thermostat is set to the right

stop (symbol  ), a room temperature of 5 °C is set as target value in

order to prevent the installation from freezing.

Overcharge protection

The switching output of all Alpha-Thermostats with microprocessor

technology is protected by an internal temperature monitoring system

in order to prevent the system from overcharge damage. In case of

an internal temperature rise due to overcharge the electronic system

automatically disconnects the output until the inside temperature

has dropped again to normal values.

Control panel

CLOSE

OPEN

1.

2.

AR 4010 S2

AC 24V/1A

1025

Lock (for locking the thermostat on

the mounting base)

T 1A

l

Individual room control, specially designed in connection with 

surface, radiator and convector heating systems.

l

Precise control response

l

Antifreeze function  5 °C

l

Valve protection function

l

Overcharge protection

l

Designs ”normally closed” (NC) and ”normally open” (NO)

l

Temperature setback 2 K (fixed)

l

Limitation of set room temperature

l

Just-in-time installation concept

l

Simple screwed connection technology in the Alpha Mounting 

Base

l

Functional design

l

12 housing colours available

Type

AR 2010 S2:  Version 230 V  –  normally closed (pure white)

AR 4010 S2:  Version 24 V  –  normally closed (pure white)

Scope of delivery (Standard)

Version: Alpha-Thermostat Standard 230 V / 24 V – normally closed:

1 x AR 2010 S2 or AR 4010 S2

1 x Installation instruction

Alternative design:

AR 2110 S2:  Version 230 V  –  normally open (pure white)

AR 4110 S2:  Version 24 V  –  normally open (pure white)

Housing colour on request

Accessories

Alpha Mounting Base AS 1000

Connection recommendations

-OEM actuator 

NC A 2004 / NC A 4004

NO A 2104 / NO A 4104

-OEM base  

without pump control:

B 2012 / B 4012

with pump control: 

B 2022 / B4022

Customer-specific version:

Customer-specific versions are available on request

Ordering information

Our staff will be glad to assist you in finding the Alpha-Thermostat

fitting your application.

Call us under: +49 (0) 53 41 - 84 75 - 0

Mikrocontr

oller T

echnology

The Alpha-Thermostat Standard is a digital room thermostat for

the control of surface heating systems with thermal actuators

(e. g. OEM actuator: A 2004 / A 4004). 

This thermostat is equipped with microprocessor technology; it

shows excellent PI controlling behaviour with increased regulating

comfort for the user.

It must be mounted to the pre-installed Alpha Mounting Base

AS 1000, onto which it can be plugged at any time and to which

it must be electrically connected. In order to avoid damage to

this valuable thermostat during the construction phase, the

system base is not included in the scope of delivery; it can be

ordered already in advance for the necessary electric installation.

Отзывы: